Turning On Comfort Recovery; Axlink Communications Screen; Switching Axlink Devices - AMX ENV-VST-C Instruction Manual

Viewstat color communicating thermostat
Hide thumbs Also See for ENV-VST-C:
Table of Contents

Advertisement

Turning on Comfort Recovery

Comfort Recovery enables you to indicate whether the heating/cooling system recovers gradually from an energy-saving setpoint
temperature to a comfort setpoint temperature. By incrementing the setpoints gradually, the heating/cooling system activates in
advance of the actual set program time so the area is at the desired temperature at the start of the program time.
Comfort Recovery begins two hours before the next programmed setpoint. During the Comfort Recovery period, every 15 minutes
the thermostat computes the difference between actual room temperature and the desired temperature of the next setpoint and set
the setpoint to the halfway point between the two.
For example, if the room temperature is 60 and the next setpoint is 70, Comfort Recovery begins and the thermostat moves the
setpoint to 65. Fifteen minutes later, the thermostat checks the setpoints again and finds the room temperature is 63 and the next
setpoint still at 70, so it changes the setpoint to 66. Fifteen minutes later, the thermostat checks the setpoints again and finds the
room temperature is 66 and the next setpoint still at 70, so it changes the setpoint to 68.
NOTE: Comfort Recovery only works when moving forward between Sleep and Wake states and between Leave and Return states.
When using Comfort Recovery between Sleep and Wake states, the thermostat uses the Sleep setpoint from the previous day and the
Wake setpoint from the current day.
If this option is disabled, heating/cooling setpoints are changed at the exact start time of the program period. Perform the
following steps to turn on the humidification and dehumidification systems:
1.
From the Main screen, press Mode/Select to access the Thermostat Mode screen.
2.
Use the navigation buttons to select Settings, and press Mode/Select. The Settings screen appears.
3.
Use the navigation buttons to select Advanced Settings. Press Mode/Select to access the Security Code screen.
4.
Enter the security code, and select Enter to access the User Preferences screen. See the Entering the Security Code on
page 30 for more information.
5.
Use the navigation buttons to highlight More, and press Mode/Select to access the second User Preferences screen.
6.
On the second User Preferences screen, use the navigation buttons to highlight More, and press Mode/Select to access the
third User Preferences screen.
7.
Use the navigation buttons to highlight Advanced Setup, and press Mode/Select to access the Advanced Setup screen.
8.
Use the navigation buttons to highlight More, and press Mode/Select to access the second Advanced Setup screen.
9.
Use the navigation buttons to highlight More, and press Mode/Select to access the third Advanced Setup screen (FIG. 44).
10. Use the navigation buttons to highlight Comfort Recovery, and press Mode/Select to toggle the option to Yes.
11. Use the navigation buttons to highlight Exit, and press Mode/Select to return to the Main screen.

AxLink Communications Screen

AxLink Communications screen
FIG. 45
The AxLink Communications screen (FIG. 45) enables you to set the address of the AxLink device with which you want the
thermostat to communicate. The AxLink address distinguishes a device on the AxLink bus from all other devices. Valid AxLink
addresses are 1-255. Address 0 belongs to the Master. The default setting for the ViewStat Color Communicating Thermostat is 1.
Pressing the Up/Down arrow buttons increases or decreases the numeric value in the highlighted box. Pressing the Mode/Select
button highlights the next box in the sequence or highlights Enter if pressed while the third box is highlighted. Use Up/Down arrow
buttons to move between Enter and Cancel. Press the Mode/Select button while Enter is highlighted to accept the new AxLink
address and return to the Advanced Setup screen.
NOTE: The current f irmware version of the thermostat appears in the lower right-hand corner of the screen.

Switching AxLink Devices

The AxLink Communications screen enables you to set the address of the AxLink device with which you want the thermostat to
communicate. The AxLink address distinguishes a device on the AxLink bus from all other devices. Valid AxLink addresses are 1-
255. Address 0 belongs to the Master. The default setting for the ViewStat Color Communicating Thermostat is 1. Perform the
following steps to switch AxLink devices:
1.
From the Main screen, press Mode/Select to access the Thermostat Mode screen.
ENV-VST-C - Instruction Manual
Advanced Thermostat Operations
42