[3-3 Functions of the Major Components of Outdoor Unit ]
Part
Symbols
name
(functions)
Sole-
SV1a
noid
Discharge-
valve
suction
bypass
SV5b
P450,
Heat
P500
exchanger
models
capacity con-
only
trol
SV9
SV10
SV11
Linear
LEV1
expan-
(SC control)
sion
valve
LEV2a
(Refrigerant
flow adjust-
ment)
LEV2b
(Refrigerant
flow adjust-
ment)
4-way
21S4a
valve
21S4b
21S4c
P450,
P500
models
only
Fan
FAN motor
FAN mo-
motor
1,2
tor 2 is
only on
the P450,
P500
models.
HWE14040
Notes
Usage
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
Controls outdoor unit heat ex-
changer capacity
High-pressure-rise prevention
Continuous heating cycle mode
Continuous heating cycle mode
Adjusts the amount of bypass flow
from the liquid pipe on the outdoor
unit during cooling
Adjusts refrigerant flow during
heating
Cut off the refrigerant flow during
continuous heating cycle
Changeover between heating and
cooling
1) Changeover between heating
and cooling
2) Controls outdoor unit heat ex-
changer capacity
Regulates the heat exchanger ca-
pacity by adjusting the operating
frequency and operating the pro-
peller fan based on the operating
pressure.
Specifications
AC220-240V
Open while being powered/
closed while not being pow-
ered
AC220-240V
Closed while being powered/
open while not being powered
Open while being powered/
closed while not being pow-
ered
Open while being powered/
closed while not being pow-
ered
Open while being powered/
closed while not being pow-
ered
DC12V
Opening of a valve driven by a
stepping motor 0-480 pulses
(direct driven type)
DC12V
Opening of a valve driven by a
stepping motor 2100 pulses
(Max. 3000 pulses)
AC220-240V
Dead: cooling cycle
Live: heating cycle
AC220-240V
Dead: cooling cycle
Outdoor unit heat exchanger
capacity at 100%
Live: heating cycle
Outdoor unit heat exchanger
capacity at 25%, 50%
or heating cycle
AC380-400V, 920W
*The P200-P400 models and
the P450 model are equipped
with different types of fan mo-
tors.
- 63 -
Check method
Continuity check
with a tester
Same as indoor
LEV
The resistance val-
ue differs from that
of the indoor LEV.
Refer to the follow-
ing page(s). [8-8
Troubleshooting
LEV Prob-
lems](page 258)
Refer to the section
"Continuity Test
with a Tester".
Continuity between
white and orange.
Continuity between
yellow, red, and
blue.
White
M
Orange
Yellow
red Blue
Continuity check
with a tester
GB