[6-9 Evaluating and Adjusting Refrigerant Charge ]
6-9-3

The Amount of Refrigerant to Be Added

The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units.
The amount necessary for extended pipe (field piping) is not included and must be added on site.
Outdoor unit model
Amount of pre-charged refrigerant in
the outdoor unit (kg)
Amount of pre-charged refrigerant in
the outdoor unit [lbs-oz]
(1) Calculation formula
The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])
When the piping length to the farthest indoor unit is shorter than 30.5 meters (100 feet)
Amount of added refrigerant (kg) = (0.29x L
Amount of added refrigerant (oz) = (3.1x L
When the piping length to the farthest indoor unit is 30.5 meters (100 feet) or longer
Amount of added refrigerant (kg) = (0.26x L
Amount of added refrigerant (oz) = (2.80x L
L
: Length of ø19.05 [3/4"] liquid pipe (m)
1
L
: Length of ø15.88 [5/8"] liquid pipe (m)
2
L
: Length of ø12.7 [1/2"] liquid pipe (m)
3
L
: Length of ø9.52 [3/8"] liquid pipe (m)
4
L
: Length of ø6.35 [1/4"] liquid pipe (m)
5
α, α': Refer to the table below.
Total capacity of
connected indoor units
-
80
81
-
160
161
-
330
331
-
390
391
-
480
481
-
630
631
-
710
711
-
800
801
-
890
891
-
1070
1071
-
1250
1251
-
Round up the calculation result to the nearest 0.1kg. (Example: 18.04kg to 18.1kg)
Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz.
(Example: 178.21oz to 179oz)
When connecting PEFY-P20VMA3-E, add 0.54 kg of refrigerant per indoor unit.
HWE14040
P200
P250
6.5
8.0
14-6
17-11
) + (0.2 x L
) + (0.12 x L
1
2
' ) +(2.15 x L
' ) + (1.29 x L
1
2
) + (0.18 x L
1
2
' ) +(1.94 x L
1
L
': Length of ø19.05 [3/4"] liquid pipe [ft]
1
L
': Length of ø15.88 [5/8"] liquid pipe [ft]
2
L
': Length of ø12.7 [1/2"] liquid pipe [ft]
3
L
': Length of ø9.52 [3/8"] liquid pipe [ft]
4
L
': Length of ø6.35 [1/4"] liquid pipe [ft]
5
α (kg)
α' (oz)
2.0
71
2.5
89
3.0
106
3.5
124
4.5
159
5.0
177
6.0
212
8.0
283
9.0
318
10.0
353
12.0
424
14.0
494
- 132 -
P300
P350
P400
11.5
11.5
11.5
25-6
25-6
25-6
) + (0.06 x L
) + (0.024 x L
3
4
' ) + (0.65 x L
3
) + (0.11 x L
) + (0.054 x L
3
' ) + (1.19 x L
' ) + (0.58 x L
2
3
P450
P500
11.8
11.8
26-1
26-1
) +α
5
' ) + α'
' ) + (0.26 x L
4
5
) + (0.021 x L
) +α
4
5
' ) + α'
' ) + (0.23 x L
4
5
GB