System With A Connection Of System Controller To Indoor-Outdoor Transmission Line - Mitsubishi Electric PUHY-P200 Service Handbook

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[2-7 Example System with an MA Remote Controller ]
2-7-5
System with a Connection of System Controller to Indoor-Outdoor
Transmission Line
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OS2
53
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OS2
56
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
(2) Cautions
1) ME remote controller and MA remote controller cannot both
be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to
a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units
that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must
be performed only on one of the outdoor units (not required
if power to the transmission line for centralized control is
supplied from a controller with a power supply function, such
as GB-50ADA).
5) Provide grounding to S terminal on the terminal block for
transmission line for centralized control (TB7) on only one of
the outdoor units.
6) A maximum of three system controllers can be connected to
the indoor-outdoor transmission line. (AE-200, AG-150A,
GB-50ADA, or G(B)-50A are not connectable.)
7) When the total number of indoor units exceeds 26, it may
not be possible to connect a system controller on the indoor-
outdoor transmission line.
In a system to which more than 18 indoor units including one
or more indoor units of 200 model or above are connected,
there may be cases in which the system controller cannot be
HWE14040
L11
Move the male connector
Leave the male
from CN41 to CN40.
connector on
SW5-1 OFF ON
CN41 as it is.
SW5-1 OFF ON
OS1
OC
52
51
TB3
TB3
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be connected
L21
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW5-1 OFF ON
SW5-1 OFF ON
OS1
OC
55
54
TB3
TB3
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be left
unconnected
L12
Group
Group
IC
IC
01
02
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
MA
L22
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1 M2
S
1 2
M1 M2
S
1 2
A B
MA
m3
Note1
Note1 LM adapters cannot be connected to the
indoor-outdoor transmission line.
System controller
A B S
connected to the indoor-outdoor transmission line.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L11+L12 200m [656ft]
L21+L22 200m [656ft]
L25 200m [656ft]
2) Transmission line for centralized control
L31+L21 200m [656ft]
3) MA remote controller wiring
Same as 2-7-1
4) Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L25+L31+L12(L11) 500m [1640ft]
L12(L11)+L31+L22(L21) 500m [1640ft]
- 40 -
Interlock operation with
the ventilation unit
Group
IC
03
TB15
TB5
TB15
TB5
1 2
M1 M2
S
1 2
M1 M2
A B
A B
MA
MA
Group
LC
IC
06
08
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
MA
2
[AWG16] or larger)
LC
07
S
GB