[2-8 Example System with an ME Remote Controller ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as 2-7-1
Shielded cable connection
Same as 2-7-1
2) Transmission line for centralized control
Same as 2-7-4
Shielded cable connection
Same as 2-7-4
3) ME remote controller wiring
ME remote controller is connectable anywhere on the in-
door-outdoor transmission line.
(5) Address setting method
Proce-
Unit or controller
dures
1
Indoor
Main unit
unit
Sub unit
2
LOSSNAY
3
ME re-
Main
mote
remote
controller
controller
Sub
remote
controller
4
Outdoor unit
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
The outdoor units are designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have
the same capacity, in the order of address from small to large).
HWE14040
4) LOSSNAY connection
5) Switch setting
Address setting
range
IC
01 to 50
Assign the smallest ad-
dress to the main unit in
the group.
Assign sequential num-
bers starting with the ad-
dress of the main unit in
the same group +1.
(Main unit address +1,
main unit address +2,
main unit address +3,
etc.)
LC
01 to 50
Assign an arbitrary but
unique address to each
of these units after as-
signing an address to all
indoor units.
RC
101 to 150
Add 100 to the main unit
address in the group
RC
151 to 200
Add 150 to the main unit
address in the group
OC
51 to 100
Assign sequential ad-
OS1
dress to the outdoor
OS2
units in the same refrig-
erant circuit. The out-
door units are
automatically designat-
ed as OC, OS1, and
OS2. (Note)
- 43 -
43
When 2 remote controllers are connected to the sys-
tem
Refer to the section on Switch Setting.
Performing a group operation (including the group
operation of units in different refrigerant circuits).
Refer to the section on Switch Setting.
Same as 2-7-4
Address setting is required as follows.
Setting method
To perform a group
operation of indoor
units that have differ-
ent functions, desig-
nate the indoor unit in
the group with the
greatest number of
functions as the main
unit.
None of these ad-
dresses may overlap
any of the indoor unit
addresses.
It is not necessary to
set the 100s digit.
To set the address
to 200, set the rota-
ry switches to 00.
To set the address to
100, set the rotary
switches to 50.
Factory
Notes
setting
00
00
101
00
GB