Error Code [7105]; Error Code [7106] - Mitsubishi Electric PUHY-P200 Service Handbook

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[7-9 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
7-9-4

Error Code [7105]

1. Error code definition
Address setting error
2. Error definition and error detection method
Erroneous setting of OC unit address
3. Cause, check method and remedy
Error source
Outdoor unit
Erroneous setting of OC unit address
The address of outdoor unit is not being set to 51 -
100.
7-9-5

Error Code [7106]

1. Error code definition
Attribute setting error
2. Error definition and error detection method
Error source
-
A remote controller for use with indoor
units, such as the MA remote controller, is
connected to the OA processing unit whose
attribute is FU.
HWE14040
Cause
Cause
- 229 -
Check method and remedy
Check that the address of OC unit is set to 51-
100.
Reset the address if it stays out of the range,
while shutting the power source off.
Check method and remedy
To operate the OA processing unit directly via a re-
mote controller for use with indoor units, such as the
MA remote controller, set the DIP SW 3-1 on the OA
processing unit to ON.
Operation Method
Interlocked operation
with the indoor unit
Direct operation via the
MA remote controller
SW3-1
OFF
ON
GB