Mitsubishi Electric PUHY-P200 Service Handbook page 56

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[2-10 Restrictions on Refrigerant Pipes ]
(2) P400 - P1350YSKB models
Outdoor unit Outdoor unit
A
B
C
Second gas refrigerant distributor
Second liquid refrigerant distributor
First liquid refrigerant distributor
First gas refrigerant distributor
First branch
Length
Between outdoor units
Total pipe length
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
Total pipe length from the first branch to the far-
thest indoor unit ( )
Height
Between indoor and outdoor units
difference
Between indoor units
Between outdoor units
*1. If the piping length exceeds 40 meters (but does not exceed 90 meters), use one-size larger pipes for all the liquid
pipes beyond 40 meters. In the figure above, the pipes whose size should be increased by one size are indicated
by "I," "c," and "d" when the piping length exceeds 40 meters at point I.
*2. If the vertical difference between indoor units exceeds 15 meters (but does not exceed 30 meters), use one-size
larger liquid pipes for the relevant indoor units. In the figure above, the pipes whose size should be increased by
one size are indicated by "J," "K," "M," "e," "f," "g,"and "i" when the "h1" exceeds 15 meters.
See the next page for the detailed description of the sample application above.
HWE14040
Note1 Install the pipe that connects the branch pipe and the outdoor units in
the way that it has a downward inclination toward the branch pipe.
Outdoor unit
Downward inclination
D
Upward inclination
(Note)
E
F
G
a
b
Indoor
Indoor
1
2
J
K
e
f
Indoor
Indoor
5
6
Operation
To indoor unit
To indoor unit
L
I
c
d
E
Indoor
Indoor
3
4
Note : "Total sum of downstream unit model numbers"
M
g
i
Indoor
Indoor
7
8
Pipe sections
A+B+C+D
A+B+C+D+E+F+G+I+J
+K+M+a+b+c+d+e+f+g
+i
A(B)+C+E+J+K+M+i
G+I+J+i
H
h1
h2
- 47 -
Provide a trap on the pipe (gas pipe only) within 2 m from the
joint pipe if the total length of the pipe that connects the joint
pipe and the outdoor unit exceeds 2 m.
To indoor unit
Joint pipe
2m [6ft]
Trap
(gas pipe
only)
To indoor unit
2m [6ft] Max.
Joint pipe
To downstream units
in the table is the sum of the model numbers
of the units after point E in the figure.
Unit: m [ft]
Allowable length of
pipes
10 [32] or less
1000 [3280] or less
165 [541] or less
(Equivalent length 190
[623] or less)
40 [131] or less
50 [164] or less
(40 [131] or below if
outdoor unit is below in-
door unit)
15 [49] or less
0.1[0.3] or less
*1
*2
GB