Mitsubishi Electric PUHY-P200 Service Handbook page 54

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[2-9 Example System with an MA and an ME Remote Controller ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as 2-7-1
Shielded cable connection
Same as 2-7-1
2) Transmission line for centralized control
Same as 2-7-4
Shielded cable connection
Same as 2-7-4
3) MA remote controller wiring
Same as 2-7-1
When 2 remote controllers are connected to the sys-
tem
(5) Address setting method
Proce-
Unit or controller
dures
1
Opera-
In-
tion
door
with the
unit
MA re-
mote
control-
ler
MA
re-
mote
con-
troller
2
Opera-
In-
tion
door
with the
unit
ME re-
mote
control-
ler
ME re-
mote
con-
troller
3
LOSSNAY
4
Outdoor unit
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
The outdoor units are designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have
the same capacity, in the order of address from small to large).
HWE14040
Address
setting
range
Main unit
IC
01 to 50
Sub unit
Main re-
MA
No
mote con-
settings
troller
required.
Sub
MA
Sub
remote
remote
controller
controller
Main unit
IC
01 to 50
Sub unit
Main re-
RC
101 to
mote con-
150
troller
Sub
RC
151 to
remote
200
controller
LC
01 to 50
OC
51 to 100
OS1
OS2
- 45 -
Same as 2-7-1
Group operation of indoor units
Same as 2-7-1
4) M-NET remote controller wiring
Same as 2-7-1
When 2 remote controllers are connected to the sys-
tem
Same as 2-7-1
Group operation of indoor units
Same as 2-7-1
5) LOSSNAY connection
Same as 2-7-4
6) Switch setting
Address setting is required as follows.
Setting method
Assign the smallest address
to the main unit in the group.
Assign sequential num-
bers starting with the ad-
dress of the main unit in
the same group +1. (Main
unit address +1, main unit
address +2, main unit ad-
dress +3, etc.)
-
Settings to be made ac-
cording to the remote con-
troller function selection
Assign the smallest ad-
dress to the main unit in
the group.
Assign sequential num-
bers starting with the ad-
dress of the main unit in
the same group +1. (Main
unit address +1, main unit
address +2, main unit ad-
dress +3, etc.)
Add 100 to the main unit
address in the group.
Add 150 to the main unit
address in the group.
Assign an arbitrary but
None of these addresses
unique address to each of
may overlap any of the in-
these units after assigning
door unit addresses.
an address to all indoor
units.
Assign sequential address
To set the address to 100,
to the outdoor units in the
set the rotary switches to 50.
same refrigerantcircuit.
The outdoor units are au-
tomatically designated as
OC, OS1, and OS2. (Note)
45
Factory
Notes
Assign an address smaller
than that of the indoor unit
that is connected to the ME
remote controller.
Enter the same indoor unit
group settings on the system
controller as the ones that
were entered on the MA re-
mote controller.
To perform a group operation
of indoor units that have dif-
ferent functions, designate
the indoor unit in the group
with the greatest number of
functions as the main unit.
Enter the indoor unit group
settings on the system con-
troller (MELANS).
Assign an address larger than
those of the indoor units that
are connected to the MA re-
mote controller.
To perform a group operation
of indoor units that have dif-
ferent functions, designate
the indoor unit in the group
with the greatest number of
functions as the main unit.
It is not necessary to set
the 100s digit.
To set the address to 200,
set the rotary switches to
00.
setting
00
Main
00
101
00
00
GB