Electra DNC series Service Manual page 88

Table of Contents

Advertisement

6.
Dry Mode
6.1.
Dry, ST or RC group or P2000 model with any group settings
Mode: Dry
Temp: Selected desired temp
Fan:
Low (automatically selected by software)
Timer: Any
I FEEL:
Any
Control function
Reduce room humidity with minimum temp. fluctuations by operating
in Cool Mode with low speed IFAN.
o
(RT - SPT) [
c]
+2
+1
0
10
-1
-2
DRY-ON
DRY
DRY-OFF
LOW
IFAN
OFF
ON
COMP
OFF
& OFAN
Max 15 minutes
ON
HE1
OFF
& HE2
ON
RV
OFF
Notes :
1. When Dry is ON, the COMP is forced OFF for 3.5 min (longer
than the 3 min Min COMP-Off time) after every 15 min of
continuous COMP operation.
2. When Dry is OFF, the COMP is forced ON for 6 min (longer
than the 3 min Min COMP-On time) after every 15 min of
continuous COMP OFF time.
3. When Dry is changed from ON to OFF or vice versa, the limits
mentioned in (1) & (2) are ignored. The COMP operation is
Service Manual - DNC Series
20
30
5 minutes COMP
ON time
3.5
min
Max 15 minutes
Note1
Revision Y05-01
CONTENT
CONTROL SYSTEM
40
50
Time [min]
6 min
Note 2
8-21