CONTROL SYSTEM
System diagnostics
Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate
diagnostic mode by the acknowledgment of 3 short beeps and lighting of COOL and HEAT
LEDs.
In diagnostic mode, system problems will be indicated by blinking of Heat & Cool LEDs.
The coding method will be as follow:
Heat led will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds. Cool
led will blink during the same 5 seconds according to the following table:
No
1
RT1 is disconnected
2
RT1 is shorted
3
RV Fault
4
RT2 is disconnected
5
RT2 is shorted
6
(Reserved)
7
RT2 temp reading doesn't change
8
RT3 is disconnected
9
RT3 is shorted
10
(Reserved)
11
RT3 temp reading doesn't change
12
RT2 & RT3 temp reading doesn't change
- ON,
- OFF
Notes:
1. If faults occur in more than one thermistor (except case number 12 on the
table above), only one fault will be indicated according to the following order:
RT3, RT2, RT1.
2. A/C will jump out to normal mode if sending a command by the R/C in the
system diagnostics mode. If this command from the R/C contain a Group ID,
this ID will become the new Group ID of the ELCON unit.
8-34
Problem
Revision Y05-01
CONTENT
1
2
3
4
Service Manual - DNC Series