Sec tio n 4 ·
Ope ra ti on
4.5 Level 2 menu - Confi guration mode
AC T I O N
To switch to confi guration mode, keep key "1" pressed
down while at the same time pressing key "2", until the
software version is displayed in the confi guration mode.
Pressing key "1" now switches to the next menu item,
and changes can be made in the respective menu item by
pressing key "2". The set value increases each time key
"2" is pressed. If the maximum value has been reached,
the value jumps to the minimum setting choice. The vari-
ous settings are highlighted in fi gure 4.5.
Software version
Clear the grid feed meter
Select the interface and confi guration of
the RS485 address
S0 interface pulse rate
Immediate start
Figure 4.5: Confi guration mode menu
Clearing the grid feed meter
When the grid feed meter is cleared, all meters ("Counter
yield", "Yield today", "Total yield", "Economy of CO
peak capacity", "Counter oper. hours", "Operating hours
today", "Total operating hours") are reset to zero.
To clear the meters, select "Yes" with key "2", and confi rm
your selection by pressing key "1". The required code is "2"
and is entered using key "2". By means of an additional con-
fi rmation with key "1", all meters are cleared. A display indi-
cating that the grid feed counters have been cleared confi rms
this action.
Meters can only be cleared.It is not possible to set the
meters.
Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN
", "Daily
2
N OT E
Choice of interface and address setting
Using the menu item "Interface", you can use key "2" to
switch between the RS232 and RS485 interfaces.
If the RS485 interface is activated, you can reach the address
setting by pressing key "1". By pressing key "2", the address
can be set in a consecutive manner from 1 to 32.
The address then jumps back to 1. The RS485 interface is used
to communicate with the Powador-proLOG. When several
inverters are connected to a Powador-proLOG, each address
may only be used once. It is, therefore, possible to monitor 32
Powador inverters with one Powador-proLOG.
S0 interface pulse rate
The S0 interface is designed as a galvanically isolated transis-
tor output. This interface is designed according to "DIN 43864
- Current interface for transmitting pulses from a pulsing meter
to a tariff metering device".
The S0 interface pulse rate can be chosen in three unit inter-
vals: 500, 1000 and 2000 pulses/kWh. Due to these toler-
ances, the emitted pulse yield may deviate from the values
on your supply grid operator's grid feed meter by up to 15 %.
AC T I O N
Settings are saved only upon exiting confi guration mode.
If 2 minutes elapse without a key being pressed, the con-
fi guration mode is automatically exited. The confi gura-
tion mode can also be immediately exited by pressing
both keys. As a confi rmation, "Settings saved" appears
on the display for 4 seconds. The settings are now per-
manently saved in the Powador inverter.
Immediate start
The inverter can also be started up without any waiting period
for the purpose of testing or for the purpose of acceptance by
your power supply company.
If the inverter is already feeding into the grid, this menu item
is not available.
AC T I O N
Keep key "2" pressed down for a short time until the
inverter switches on (relays switch audibly) and the green
grid feed LED (2) lights up. If there is insuffi cient solar
generator power, the inverter stops feeding into the grid
after a short period of time.