INSTALLATION AND INSTRUCTIONS

1.2 Installation of the inverter

Install the inverter on a strong surface securely with bolts.
Leave enough clearances and take cooling measures.
Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
Install the inverter on a nonflammable surface.
When encasing multiple inverters, install them in parallel as a cooling measure.
*1
For the FR-A820-00250(3.7K) or lower, the FR-A840-00126(3.7K) or lower, and the FR-A846-00126(3.7K) or lower allow 1cm or more clearance.
*2
When using the FR-A820-01250(22K) or lower and FR-A840-00620(22K) or lower at the surrounding air temperature of 40°C or less (30°C or less for the
SLD rated inverter), side-by-side installation (0cm clearance) is available.
*3
For replacing the cooling fan of the FR-A840-04320(160K) or higher, and of the FR-A842 models, 30cm of space is necessary in front of the inverter.
Refer to the Instruction Manual for fan replacement.

1.3 Environment

Before installation, check that the environment meets following specifications:
Surrounding air
*6
temperature
Ambient humidity
Storage temperature
Atmosphere
Altitude
Vibration
*4
Temperature applicable for a short time, e.g. in transit.
*5
For the installation at an altitude above 1,000m up to 2,500m, derate the rated current 3% per 500 m.
*6
Surrounding air temperature is a temperature measured at a measurement position in an enclosure. Ambient temperature is a
temperature outside an enclosure.
*7
2
2.9m/s
or less for the FR-A840-04320(160K) or higher
2
Fix six positions for the FR-A840-
04320(160K) or higher and for
the FR-A842 models (separated
converter type).
FR-A820-03160(55K) or lower,
FR-A840-01800(55K) or lower
FR-A846
5cm
*1, *2
Vertical
LD, ND (initial setting), HD ratings: -10°C to +50°C (non-freezing)
SLD rating: -10°C to +40°C (non-freezing)
IP55 compatible models: -10°C to +40°C (non-freezing)
With circuit board coating, IP55 compatible models: 95% RH or less (non-condensing),
Without circuit board coating: 90% RH or less (non-condensing)
*4
20°C to +65°C
Indoors (No corrosive and flammable gases, oil mist, dust and dirt)
Maximum 2,500 m above sea level
*7
5.9m/s² or less
at 10 to 55Hz (directions of X, Y, Z axes)
Clearances (front view)
FR-A820-03800(75K) or lower,
FR-A840-02160(75K) or lower
FR-A842
10cm
20cm
5cm
10cm
*1, *2
10cm
20cm
*5
Clearances (side view)
10cm
5cm
*1, *3
Enclosure
x = Measurement position
5 cm
5 cm
5 cm