Programme Dry Function - Daikin FTKS20CVMB Service Manual

Inverter pair wall mounted type
Hide thumbs Also See for FTKS20CVMB:
Table of Contents

Advertisement

Main Functions
1.4

Programme Dry Function

Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls both the temperature and air flow volume, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
The microcomputer automatically sets the temperature and fan settings. The difference
In Case of
between the room temperature at startup and the temperature set by the microcomputer is
Inverter Units
divided into two zones. Then, the unit operates in the dry mode with an appropriate capacity for
each zone to maintain the temperature and humidity at a comfortable level.
Room temperature at
startup
48
Temperature (ON point)
at which operation starts
Room temperature at
24°C
startup
18°C
18°C
17°C
ON point
0.5°C
Frequency
switching
point
OFF point
Compressor
control
Extra-low air flow
Indoor unit fan
Low air flow
LHz indicates low frequency. Item marked with varies depending on models.
Frequency switching
point
5 min
Stop
LHz
*55Hz
Stop
SiENBE04-401A
Temperature difference
for operation stop
0.5°C
5 min
Stop
LHz
LHz
*55Hz
Extra-low air flow
Stop
Low air flow
Function and Control
1.5°C
1.0°C
Stop
Stop
(R1359)