Thermistor Resistance Check - Daikin FTKS20CVMB Service Manual

Inverter pair wall mounted type
Hide thumbs Also See for FTKS20CVMB:
Table of Contents

Advertisement

Check

5.1.3 Thermistor Resistance Check

Remove the connectors of the thermistors on the PCB, and measure the resistance of each
Check No.6
thermistor using tester.
The relationship between normal temperature and resistance is shown in the graph and the
table below.
Temperature (°C)
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
140
Thermistor R25°C=20kΩ B=3950
211.0 (kΩ)
150
116.5
88
67.2
51.9
40
31.8
25
20
16
13
10.6
8.7
7.2
(R25=20kΩ, B=3950)
(kΩ)
150
100
50
-15
0
Tester
Resistance range
15
30
45
(°C)
SiENBE04-401A
(R1437)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents