INSTALLATION AND MAINTENANCE INSTRUCTIONS
R
FIGHTER 600P
MOS GB 0413-2
611424
FIGHTER 600P
1, 2, ...

Advertisement

Table of Contents
loading

Summary of Contents for Nibe FIGHTER 600P

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS FIGHTER 600P MOS GB 0413-2 611424 FIGHTER 600P 1, 2, ...
  • Page 3: Table Of Contents

    Maximum boiler and radiator volumes ....12 Setting the automatic heating control Inspection of the installation ........ 12 system Temperatures in FIGHTER 600P ......12 Heating curve offset -2 ........20 Channel description ..........13 Heating curve offset 0 .......... 20 Pipe connections Heating curve offset +2 ........
  • Page 4: Concise Product Description

    FIGHTER 600P you should read through the For Home Owners section in this Installation and Maintenance Instruction. FIGHTER 600P is a combined exhaust air and out- door air heat pump. This means it utilises energy in ventilation air and outdoor air when this does not fall below -5 °C.
  • Page 5: System Description

    For Home Owners System description Principle of operation FIGHTER 600P consists of an electric boiler with enam- elled water heater and a heat pump that recovers energy Vented air Outdoor air Exhaust air Avluft Uteluft Frånluft from ventilation air and outdoor air when this is - 5 °C or warmer.
  • Page 6: Front Panel

    Flashing Immersion heater or part of the for example, a floor heating system. immersion heater blocked via cen- tralised load control/tariff control or due to a 2 hour delay with start of FIGHTER 600P. FIGHTER 600P...
  • Page 7: Functions On The Front Panel

    Pressing it once more stops the circulation goes out in this operating mode. pump as well. However, note that the circulation NOTE! If FIGHTER 600P is installed in a large pump is operational during hot water heating. house so that no outdoor air is utilised only...
  • Page 8: Room Temperature

    If the room temperature is low, increase the heating curve selection setting by one step. FIGHTER 600P offers the possibility to block immer- If the room temperature is high, reduce the heating sion heater operations as a function of the outdoor curve selection setting by one step.
  • Page 9: Basic Values For The Automatic Heating Control System

    A suitable setting on the Increase/reduce knob is - 2 for radiator systems and -1 for floor heating. - 10 - 20 - 30 - 40 °C HEATING OUTSIDE TEMPERATURE CURVE OFFSET Diagram with offset +2 FIGHTER 600P...
  • Page 10: Maintenance Routines General

    Cleaning the outdoor air damper When cleaning the outer wall grille even the outdoor air damper in FIGHTER 600P should be cleaned. First switch off the heat pump. Now open the upper service cover as described in the section Maintenance rou- tines - Cleaning the air filter.
  • Page 11: Cleaning The Ventilation Devices

    - High extract air temperature. It is normal that the extract air temperature varies. Sacrificial anode test FIGHTER 600P has two safety valves, one for the heating system and one for the water heater. ANODEN-TESTER 1, 2, ...
  • Page 12: Low Temperature Or A Lack Of Hot Water

    Automatic heating control system settings not cor- High pressure pressostat rect. The reversing valve (43) is set to manual mode. If the operating disturbance cannot be rectified by means of the above an installation engineer should be called. If necessary set the switch to FIGHTER 600P...
  • Page 13: Indications On The Display

    It is usually easier to start the circulation pump with FIGHTER 600P running, switch (8) set to “1”. If help- ing the circulation pump to start is performed with FIGHTER 600P running, be prepared for the screw- driver to jerk when the pump starts.
  • Page 14: General Information For The Installer

    Route pipes so they are not fixed to an internal wall that backs on to a bedroom or living room. FIGHTER 600P has a venting screw located on the front edge at the top. This should be easily accessible, which should be considered during installation.
  • Page 15: Channel Description

    Control reverts to only showing channels 1 to 11 after tion approximately 4 hours or by changing the value from 00 Normal mode, ventilation adjustment not activated 01 to 00 under channel 11. 01 Highest fan speed, outdoor air damper closed FIGHTER 600P...
  • Page 16: Pipe Connections

    Pipe connections General Docking Pipe installation must be carried out in accordance Other heat sources can be docked to FIGHTER 600P. with current norms and directives. Accessories are needed. Contact NIBE AB for infor- mation. The system requires a low-temperature design of the radiator circuit.
  • Page 17: Ventilation Connection

    Duct connections should be made via flexible hoses, which must be installed so that they are easy to replace. FIGHTER 600P is connected so that all ventilation air The extract air and outdoor air ducts are to be insulated except the kitchen fan passes the evaporator (62) in using diffusion-proof material along their entire lengths.
  • Page 18: Electrical Connections

    The temperature limiter is reset by firmly pressing in the sensor capsule. the rubber membrane. 1, 2, ... – – U-PUMPE PARALLEL – RUNDSTEUERUNG FERNSTEUERUNG AUSSENFÜHLER SCHUTZKLEINSPANNUNG SELV Max phase current Output Max load Group fuse (kW) phase (A) 12.8 14.9 19.2 FIGHTER 600P...
  • Page 19: Remote/Room Control

    The microprocessor in FIGHTER 600P corrects the originally selected setting for Heating curve offset by External switch or External three steps downwards.
  • Page 20: Commissioning And Adjusting

    (35). See the section Pipe connec- 3, 4, 5 and 6 A and B tions - Pump and pressure drop diagram. Make (no electrical output available) sure that the switch is not in an intermediate posi- tion. FIGHTER 600P...
  • Page 21: Drying Process

    11. Channel 12 up to channel 27 are dries at the right rate.FIGHTER 600P is equipped with this function. This means you can set a program so the service channels and may only be managed by that a constant flow temperature is obtained during a a professional.
  • Page 22: Setting The Automatic Heating Control System

    For the Installer Setting the automatic heating control system Heating curve offset -2 Setting using diagrams FIGHTER 600P is equipped with outdoor temperature HEATING CURVE KURVLUTNING controlled automatic controls. This means the flow °C temperature is regulated in relation to the current out- 15 14 13 12 door temperature.
  • Page 23: Service

    Service - Opening the cover to the distribu- tion box. The normal position on the miniature circuit-breaker (7) is “1” (left). The above may only be carried out by persons with the relevant expertise. Note the distribu- tion box contains live parts. FIGHTER 600P...
  • Page 24: Cleaning The Circulation Pump

    - Emptying the water heater. Dismantle the inspection cover (58). Replace the sacrificial anode in the inspection cover. Re-assemble in the reverse order. Sacrificial anode replacement can be eliminated if a direct current anode is fitted. FIGHTER 600P...
  • Page 25: Dimensions

    Measuring principle Copper pipe Compression ring Klämring Cu-rör A, B and C: See “Connection” in the “List of components”. When running pipes in the hatched area, make sure there is space to change the expansion vessel. FIGHTER 600P...
  • Page 26: Electrical Circuit Diagram

    6,0 kW brun 6 5 4 3 2 1 6 5 4 3 2 1 1B 1A L3 L2 L1 N – 220 V 12 V 6 5 4 3 2 1 6 5 4 3 2 1 FIGHTER 600P...
  • Page 27: Kw (Output On Delivery)

    NOTE! In this output step only 2 kW is obtained in standby mode. 2 x 1 kW White 3 x 2 kW Brown 9.0 kW (delivery output) All cables are connected to the immersion heater. 3 x 1 kW White 3 x 2 kW Brown FIGHTER 600P...
  • Page 28: Component Locations

    For the Installer Component placement 75 19 Hidden! Dold! 54 12 57 14 Hidden! Honywell 9840 UC40 13 6 sec, 6 VA VALVE ACTUATOR 220-240 VAC 50/60 HZ T65 TS110 IP40 FIGHTER 600P...
  • Page 29 For the Installer Component placement 31 30 1, 2, ... 1, 2, ... Hidden! Dold! FIGHTER 600P...
  • Page 30: List Of Components

    94 Ventilation connection outdoor air ........Ø 125 mm ....2109 ..154 ..420 95 Overflow pipe, safety valve water heater 96 Overflow pipe, safety valve heating 97 Condensation water outlet, fan box 98 Overflow water discharge ..........PVC-pipe Ø 32 mm (outside diameter) 99 Collection funnel, waste water FIGHTER 600P...
  • Page 31: Technical Specifications

    2,45 MPa (24.5 (bar) Breaking value, low pressure pressostat 0,15 MPa (1.5 (bar) Fuse pressure in boiler section 0.25 MPa (2.5 (bar) Refrigerant volume 380 g Refrigerant type R290 (propane) Sound level in the boiler house 40 – 45 dBA FIGHTER 600P...
  • Page 32: Docking

    For the Installer Docking Docking to a gas boiler FIGHTER 600P is suitable for docking to a gas boiler. The electrical connection between the gas boiler and This then replaces the immersion heater in the heat the heat pump is made via a two-pole cable. When the pump.
  • Page 33: Docking To An Accumulator Tank

    For the Installer Docking Docking to the accumulator tank In order to utilise special tariffs the FIGHTER 600P water to the FIGHTER’s heating circuit. This takes can be supplemented with an accumulator tank (with place until there is no longer a need of the energy sup- immersion heater), which supplies a heat supplement plement.
  • Page 34: Installation Method

    Return supplier’s instructions * Including any distribution fittings Radiator Radiator 1, 2, ... 1, 2, ... Supply 1, 2, ... Bypass valve Return SF Particle filter M Shunt Floor heating* FIGHTER 600P...