For Home Owners section in this Installation and Maintenance Instruction. FIGHTER 1210 is a heat pump central for the production of heating and domestic hot water in detached and terrace houses. The ground, rock or lakes can be used as the heat source.
For Home Owners System description Principle of operation The FIGHTER 1210 consists of a heat pump, water The brine emits its heat to the refrigerant in the heat heater, electrical element, circulation pumps, a soft- pump’s evaporator. It then vaporises and is com- start relay and control computer with display.
For Home Owners Front panel Front panel Display WW-out 49(50) °C Hot-water 51 °C Function keys Indicator lamps Increase/reduce heat Switch NOTE! Make sure there is water in the heat pump before turning the switch (A) into position 1 or FIGHTER 1210...
Press the Operating mode button again. LEDs: Room heating: Not lit Hot water: Lit during hot water charging Additional heat Not lit The system returns to normal mode the next time the Operating mode button is pressed. FIGHTER 1210...
One scale marking corre- This adjustment takes place automatically, since the sponds to a change of about one degree in the room FIGHTER 1210 is equipped with a control computer temperature. for optimal, safe operation. However, the heat pump must first be given the correct basic setting.
There are four stages to heat production, one for the heat pump and three for the electrical module. The output of the electrical element as supplied is 6 kW (FIGHTER 1210 – 4, 3 kW) but it can be rewired to give 9 kW FIGHTER 1210...
For Home Owners Control Available information and on-display settings FIGHTER 1210 has a two-line LCD display. The heat pump can be set via this display and its associated buttons. WW-in 37(53) °C HW start 49(44) °C Channel selection The Channel button lets you browse through the...
The preset value is 45 °C. Therefore this value nel is pressed. Press Increase to change language. must normally increased when When the required language is selected, press the radiator system is used. Channel button. You then return to display 1. FIGHTER 1210...
If the heat pump is replaced, the installation must be inspected again. Installation FIGHTER 1210 is placed on a firm base, preferably a Electric boiler mode concrete floor or foundation. Install FIGHTER 1210 with its back to an outside wall, ideally in a room where noise does not matter.
[P] Stop temperature for water heater charging first stage of additional heat (TS) is allowed to be when operating with additional heat only. switched on. Basic setting: 50. Basic setting: 300. Setting range: 50 – 2500. Setting range: 10 – 70. FIGHTER 1210...
Option 2 – 5 may not be used. button was pushed. Select the right operating mode before Add-drift Parallel is activated. ((Add-drift locks the operating mode function). Setting of Increase/Reduce heat potentiometer to displace the heating curve (parallel offset). Operating mode button FIGHTER 1210...
Page 15
This is so the floor dries correctly. FIGHTER 1210 has a function for this drying process. The process can be divided into two periods where the number of days and temperature are set for respective periods.
60 °C from the (as close to the heat pump as possible), and particle heat pump. Since the FIGHTER 1210 is not fitted with filter (supplied) are fitted. shut-off valves, these must be fitted outside of the When connecting to a system with thermostats on all heat pump to make future servicing easier.
Brine in Brine out FIGHTER 1210 Free cooling FIGHTER 1210 COMPACT The equipment can be supplemented with a fan coil unit to make the connection of ambient cold possible. To avoid condensation, all pipes and other cold sur- faces must be isolated with diffusion-proof material.
The heat pump is connected on terminal (9) to 400 V 3-phase, neutral + earth via a distribution board with fuses. FIGHTER 1210 does not include an isolator switch on the incoming electrical supply. The installation must be preceded by a circuit-breaker with at least a 3 mm breaking gap.
Output as set at the factory immersion heater FIGHTER 1210 has an immersion heater which is connected for 6 kW on delivery (FIGHTER 1210 – 4, 3 Disconnection of the entire electrical power is kW immersion heater output). The change-over to oth-...
Remove the filler hoses and refit the level vessel. Fill the required pressure is reached and then vented. the vessel about three-quarters full with the fluid. Now shut the filling plug and open the valve under the ves- sel. Reset normal mode by setting EB to “0”. FIGHTER 1210...
A high difference could depend on a low heat medium flow. Fill in the commissioning report on page 2. Set the control computer to suit the needs of the building. FIGHTER 1210...
For the Installer Setting the heating controls Setting using diagrams Offset heating curve -2 The heating control system of the FIGHTER 1210 is HEATING CURVE KURVLUTNING controlled by the outside temperature. This means the °C supply temperature is regulated in relation to the cur- 15 14 13 12 rent outdoor temperature.
CPU-unit 4 kW Heat Heat medium medium Operating pressostat Low pressure Brine in Brine out water return flow CPU-card CPU-unit 5 – 10 kW Heat Heat Low pressure Operating pressostat Brine in Brine out medium medium water return flow CPU-card FIGHTER 1210...
An area of 800 mm is required in front of the FIGHTER 1210 for service work. When FLM 30 is fitted on FIGHTER 1210 the distance to the wall should be 50 mm.
Cut-out value pressostat LP (bar) Difference pressostat LP (bar) +1,5 Net weight (kg) Compressor output only. ** Refers to the brine flow temperature/heat medium flow temperature in accordance with EN 255. *** With feet and connections dismantled the height is 1890 mm. FIGHTER 1210...
Accessories Load monitor EBV 200 ROOM SENSOR RG 20 Part no 418,346 Part no 418,345 Exhaust air module FLM 30 Part nr 089 268 Level monitor NV 10 Part no 089 315 Sacrificial anode Part no 089 308 FIGHTER 1210...
Increase/reduce heat. should always be stated with all Action: Adjust the setting. correspondence with NIBE. 689_ _ _ _ _ _ _ _ _ _ _ If the operating disturbance cannot be rectified by means of the above an installation engineer should be called.
“out error” NOTE! The fault status must not be repeatedly reset, as there is a risk of overheating the motor windings. If the operating disturbance cannot be rectified by means of the above an installation engineer should be called. FIGHTER 1210...
It is usually easier to start the circulation pump with FIGHTER 1210 running, switch (8) set to 1. If helping the circulation pump to start is performed with FIGHT- ER 1210 running, be prepared for the screwdriver to jerk when the pump starts.
Page 40
Tel:1684 73249 NIBE Energietechniek B.V Fax: 1684 76642 Hofstraat 18 E-mail: info@nibeboilers.nl 4797 AC WILLEMSTAD www.nibeboilers.nl NIBE-BIAWAR Sp. z o. o. Tel: 85 662 84 90 Alejá Jána Pawła II 57 Fax: 85 662 84 16 15-703 BIAŁYSTOK www.biawar.com.pl 17-NIP: 542-02-00-292...