MOS GB 0850-6
INSTALLATION AND MAINTENANCE INSTRUCTIONS
FIGHTER 640P
FIGHTER 640P
711114
1, 2, ...

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FIGHTER 640P and is the answer not in the manual?

Questions and answers

Summary of Contents for Nibe FIGHTER 640P

  • Page 1 MOS GB 0850-6 INSTALLATION AND MAINTENANCE INSTRUCTIONS FIGHTER 640P FIGHTER 640P 711114 1, 2, ...
  • Page 3: Table Of Contents

    Maximum boiler and radiator volumes _______________ 12 Technical Data ___________________________ 34 Inspection of the installation _______________________ 12 Enclosed kit _____________________________ 34 Temperatures in FIGHTER 640P _____________________ 12 Channel description_______________________________ 12 Accessories _____________________________ 34 Pipe connections ________________________ 14 Docking ________________________________ 35...
  • Page 4: For Home Owners

    General General In order to get the ultimate benefit from your heat pump FIGHTER 640P you should read through the “For Home Owners” section in this Installation and Maintenance Instruction. FIGHTER 640P is a combined exhaust air and outdoor air heat pump. This means it utilises energy in ventilation air and outdoor air when this does not fall below -5 °C.
  • Page 5: System Description

    For Home Owners System description System description Principle of operation Exhaust air Extract air Outdoor air FIGHTER 640P consists of an electric boiler with enam- Avluft Uteluft Frånluft Avluft Uteluft Frånluft elled water heater and a heat pump that recovers energy from ventilation air and outdoor air when this is - 5 °C or...
  • Page 6: Front Panel

    Flashing Immersion heater or part of the immersion to prevent any damage due to a too heater blocked via centralised load control/ high temperature with, for example, tariff control or due to a 2 hour delay with a floor heating system. start of FIGHTER 640P. FIGHTER 640P...
  • Page 7 Note! If FIGHTER 640P is installed in a large house this chosen operating mode in the event of a restart, so that no outdoor air is utilised only exhaust air, the for example after a power failure.
  • Page 8: Room Temperature

    If the required room temperature is not obtained, readjust- Blocking the immersion heater ment may be necessary. FIGHTER 640P offers the possibility of blocking immersion Note! Wait one day between settings so that the tempera- heater operations as a function of the outdoor tempera- tures have time to stabilise.
  • Page 9: Ventilation

    A suitable setting on the “Increase/reduce heat” knob is - 2 for radiator systems and -1 for floor heating. - 40 °C - 10 - 20 - 30 OUTDOOR TEMPERATURE FÖRSKJUTNING UTETEMPERATUR HEATING CURVE OFFSET VÄRMEKURVA (+2) Diagram with offset + 2 FIGHTER 640P...
  • Page 10: Maintenance Routines

    The numbers in brackets refer to the section “Component locations”. When cleaning the outer wall grille even the outdoor air damper in FIGHTER 640P should be cleaned. First switch Cleaning the air filter off the heat pump. Now open the upper service cover as described in the section “Maintenance routines”...
  • Page 11: Cleaning The Ventilation Devices

    11 Abweichung von Vorlauftemperatur 12 Service A Art.nr. 611971 13 Service B 14 Service C FIGHTER 640P has two safety valves, one for the heating Kontrollknopf drücken 15 Service D 16 Service E system and one for the water heater.
  • Page 12: Dealing With Malfunctions

    MCB (7) tripped. See the section “Service” – heat pump are off. “Resetting the miniature circuit breakers”. The numerical display is off, FIGHTER 640P • Closed or throttled filler valve (46) on the water heater. does not produce hot water.
  • Page 13: Indications On The Numerical Display

    “Maintenance routines” – “Cleaning the air filter”. It is usually easier to start the circulation pump with FIGHTER 640P running, switch (8) set to “1”. If helping the circulation pump to start is performed with FIGHTER 640P running, be prepared for the screwdriver to jerk when the pump starts.
  • Page 14: For The Installer

    Calculated flow temperature Route pipes so they are not fixed to an internal wall that backs on to a bedroom or living room. FIGHTER 640P has a venting screw located on the front Outdoor temp. Utetemperatur edge at the top. This should be easily accessible, which °C...
  • Page 15 04 (A) Basic, with closed damper 27 Selected temperature in step 2 regarding the drying Note! process It takes two minutes before the damper changes position fully and this time must pass before the airflow reading/ adjustment is made. FIGHTER 640P...
  • Page 16: Pipe Connections

    55 litres in the boiler section. mounting and EMINENT 35-100 for wall-mounting. PROPPNING The pressure vessel in the FIGHTER 640P is approved for 1. Split the valve coupling. max 9.0 bar (0.9 MPa) in the water heater and 2.5 bar 2.
  • Page 17: Installation Method

    Flow line Bypass valve Framledning Bypassventil Supply Bypass valve Return line Returledning Return Control valve with motor The bypass valve must be positioned as far Floor heating* Golvvärme* Floor heating* away from the heat pump as possible. SVENSKA ENGELSKA FIGHTER 640P...
  • Page 18: Ventilation Connection

    The cables must then be connected to the earthing studs on top of the top FIGHTER 640P is connected so that all ventilation air ex- cover. cept the kitchen fan passes the evaporator (62) in the heat pump.
  • Page 19: Fan Diagram

    H), and read off the fan output on the right-hand axis. In this instance, the fan output is 70 W at an airflow of 200 m Exhaust air duct The kitchen flue must not be connected to FIGHTER 640P. Adjustment See the section “Setting the ventilation”. FIGHTER 640P...
  • Page 20: Electrical Connections

    The supply to the heat pump is connected to terminal (9) • Open the protective cover on the distribution box (see via a strain relief. FIGHTER 640P does not include an isola- section “Service”- “Opening the cover on the distribu- tor switch on the incoming electrical supply. The installa- tion box”).
  • Page 21: Connecting The Outdoor Sensor

    SCHUTZKLEINSPANNUNG SELV house, where FIGHTER 640P is installed. The risk of smok- sun. The sensor is connected with a two-wire cable to ter- ing is reduced by the stove monitor sensing the pres- minal (14) positions “7”...
  • Page 22: External Compressor Supply

    9, pos “1A-1B”. 1B L3 L2 L1 1A 1B L3 L2 L1 Miscellaneous Immersion Övrigt Elpatron heater 1B L3 L2 L1 1A 1B L3 L2 L1 Övrigt Elpatron 1A 1B L3 L2 L1 FIGHTER 640P...
  • Page 23: Commissioning And Adjusting

    20 minutes. • Set the design capacity on the circulation pump using its switch (35). See the section “Pipe connections” – “Pump and pressure drop diagram”. Make sure that the switch is not in an intermediate position. FIGHTER 640P...
  • Page 24: Setting The Ventilation

    Press the “Operating mode” button yet again so that If reduced ventilation is required when the compressor is the display shows “00” and FIGHTER 640P will revert not running (basic ventilation), the following must be car- to normal mode (return also happens automatically ried out.
  • Page 25: Drying Process

    The setting options for the number of days is one to five and for the temperature 15 to 50 °C. Once the set number of days have elapsed FIGHTER 640P automatically reverts to normal functionality. If the power is cut, for example, by the power switch being turned to “0”...
  • Page 26: Setting The Automatic Heating Control System24

    °C 15 14 13 12 Setting with diagrams FIGHTER 640P is equipped with outdoor temperature con- trolled automatic devices. This means the flow temperature is regulated in relation to the current outdoor temperature. The relationship between outdoor temperature and flow temperature is set with the “Heating curve selection”...
  • Page 27: Service

    If this is not sufficient, loosen a pipe coupling on the hot water side. Draining the heating system The heating system is drained through the drain valve (51). This is located behind the lower service cover. FIGHTER 640P...
  • Page 28: Dimensions

    (SELV) Ø 16 A clear space of 500 mm is needed in front of the heat pump for servicing. Avoid routing pipes within the hatched Undvik rördragning inom streckmarkerat area to facilitate service område för att underlätta service FIGHTER 640P...
  • Page 29: Electrical Circuit Diagram

    For the Installer Electrical circuit diagram Electrical circuit diagram FIGHTER 640P...
  • Page 30 For the Installer Electrical circuit diagram FIGHTER 640P...
  • Page 31 For the Installer Electrical circuit diagram FIGHTER 640P...
  • Page 32 For the Installer Electrical circuit diagram FIGHTER 640P...
  • Page 33: Component Locations

    For the Installer Component locations Component locations Hidden FIGHTER 640P...
  • Page 34 For the Installer Component locations 1, 2, ... Art.nr. 611971 Art.nr. 611971 FIGHTER 640P...
  • Page 35: List Of Components

    95 Overflow pipe, safety valve water heater 96 Overflow pipe, safety valve heating 97 Condensation water outlet, fan box 98 Overflow water discharge PVC-pipe Ø 32 mm (outside diameter) 99 Collection funnel, waste water 100 Particle filter 110 Auxiliary relay 158 Fan card FIGHTER 640P...
  • Page 36: Technical Data

    Used if the heat pump is to be split up and the modules With temporary high current drain the load monitor each placed individually. Contains splitter wiring, pipe con- disables parts of FIGHTER 640p’s electrical output to pro- nections, hoses for condensation water and evacuation as tect the building’s main fuses.
  • Page 37: Docking

    FIGHTER are removed and insulated. FIGHTER 640P is suitable for docking to a gas boiler. This When energy is retrieved from the gas boiler 1105: then replaces the immersion heater in the heat pump.
  • Page 38: Docking To The Accumulator Tank

    FIGHTER 600P Docking to the accumulator tank Equipment In order to utilise special tariffs the FIGHTER 640P can be In addition to FIGHTER 640P the system consists of one (or supplemented with an accumulator tank (with immersion more) accumulator tank (s) PS 500 and a docking kit PSP...
  • Page 40 Tel: +43 (0)7662 8963-0 Fax: +43 (0)7662 8963-44 E-mail: mail@knv.at www.knv.at NIBE Wärmetechnik AG, Winterthurerstrasse 710, CH-8247 Flurlingen Tel: (52) 647 00 30 Fax: (52) 647 00 31 E-mail: info@nibe.ch www.nibe.ch Druzstevni zavody Drazice s.r.o, Drazice 69, CZ - 294 71 Benatky nad Jizerou Tel: +420 326 373 801 Fax: +420 326 373 803 E-mail: nibe@nibe.cz www.nibe.cz...