Docking List of components ..........24 General ..............9 Sound pressure levels FIGHTER 2005 docked with SMO 10 ...... 9 Sound pressure levels ......... 25 Several FIGHTER 2005s docked with SMO 10 ..10 Dimensions FIGHTER 2005 docked with wood-fired boiler and hot water heater .........
For Home Owners General In order to get the ultimate benefit from your heat pump FIGHTER 2005 you should read through the For Home Owners section in this Installation and Maintenance Instruction. FIGHTER 2005 is a base heat pump for heating small houses, apartment blocks and small industrial premises.
FIGHTER 2005 is started by a start signal from another controller, return line sensor or thermostat. FIGHTER 2005 can also be controlled by a specially designed controller, SMO 10*.
For Home Owners Maintenance routines Maintenance of FIGHTER 2005 FIGHTER 2005 is equipped with control and monitor- If necessary the outer casing can be cleaned using a ing equipment, however some exterior maintenance is damp cloth. Care must be exercised so that the plastic still necessary.
Action: Check the settings on the control equip- ment. NOTE! Cause: Fuse has tripped. As FIGHTER 2005 can be connected Action: Replace the fuse or reset the MCB. If the to a large number of external units, fuse trips again the installation engineer should be contacted.
FIGHTER 2005 has an integrated electronic return FIGHTER 2005 is placed outdoors on a firm base, line sensor that limits the return temperature. The flow preferable a concrete foundation. FIGHTER 2005 and return line sensors are fitted during installation.
Shutoff and drain valves are fitted so that FIGHTER 2005 can be emptied in the event of prolonged power failures. The supplied flexible hoses act as vibration dampers.
For the Installer Docking General FIGHTER 2005 can be installed in several different When docking with FIGHTER 2005, a total water vol- ways. The safety equipment must be installed in ume, in the boiler and accumulator, of at least 20 litres...
FIGHTER 2005 works with floating FIGHTER 2005 VP1 is connected in at position (44) condensing against the heating system and prioritises using the enclosed modular cable (15m) from SMO 10.
For the Installer Docking FIGHTER 2005 docked with wood-fired boiler and hot water heater (fixed condensing) External or exist- Extern alt befintlig regler- ing control equip- utrustning. ment FIGHTER 2005 SÄV Wood-fired boiler VVB / ACK Vedpanna FIGHTER 2005 charges the hot water heater/accumu- accumulator tank.
■ If a miniature circuit breaker is used this should have a motor characteristic “D” (compressor opera- tion). For MCB size see Technical Specifications. ■ The FIGHTER 2005 does not include an isolator switch on the incoming electrical supply. The instal- Hjälpkontaktor lation must be preceded by a circuit-breaker with at least a 3 mm breaking gap.
L2 L3 nal block (11) the pump is controlled by FIGHT- of FIGHTER 2005. If the FIGHTER 2005 faces south ER 2005. Pump activity depends on the status of or to the west, where there is a risk of intensive heat-...
This thermostat should be of the break- ing type (NC) when the set temperature has been when FIGHTER 2005 is reached. The contactor should be potential free. controlled by SMO 10.
Electrical connection Example of addition Additional heat/downtime connection FIGHTER 2005 is equipped with a potential free con- tactor intended for additional heat: Max 250V 2A. Basic electrical circuit diagram for connection of auxil- The setting of the outdoor air temperature (balance iary relays for additional heat and downtime.
Adjustment, charge flow ■ Fill in the commissioning report on page 2. Soft-start relay NOTE! FIGHTER 2005 is equipped with a soft-start relay (97) The live external control must be that limits the inrush current for the compressor. taken into consideration when The compressor must not be forced to start with peri- ods shorter than 1 start per 15 minutes.
5 minutes after start, or about 5 min- 1 flow temperature 35° utes after defrosting with a cold outdoor temperature. 2 flow temperature 45° ∆T FIGHTER 2005 -8 3 flow temperature 55° ∆T 20,0 20,0 18,0 18,0...
11 Manual activation of the defrosting. Change the follows: value 0 to 1 and confirm using the Enter button. 00 Shows the set operating mode on FIGHTER 2005. 01 Normal operation. 12 Restore factory default settings. Change the value 02 Defrosting.
Page 22
120 minutes. Address for communication with SMO 10. This should 1 / 1 / 1 be selected so that each FIGHTER 2005 in the sys- tem has a unique address (1–9) for communication 29 Measured temperature on the return line sensor.
For the Installer Electrical circuit diagram T5AH common alarm RC L1 PE 3 PE 2 ** Circulation pump for heat medium controlled from FIGHTER 2005, not included with the delivery. FIGHTER 2005...
39 Enter button 102 Cable gland, sensor 40 Reset button 103 Serial number 41 High pressure pressostat 42 Service connection, high pressure The component list refers to all types of heat pump, see respective component location pictures for information. FIGHTER 2005...
For the Installer Sound pressure levels Sound pressure levels FIGHTER 2005 is usually placed next to a house wall, which gives a directed sound distribution that should be considered. Accordingly, you should always attempt to find a placement on the side that faces the least sound sensitive neighbouring area.
Fritt utrymme Free space Fritt utrymme Min. avstånd Min. distance Min. avstånd vid användning when using av flera F 2010 vid användning several F 2005 av flera F 2010 Fritt utrymme framför Free space in front Fritt utrymme framför FIGHTER 2005...
For the Installer Enclosed kit Particle filter R25 L E K 2 flexible hoses (R25) with 4 seals 4 adjustable feet with holders Heating pipe paste Aluminium tape Cable ties, 4 FIGHTER 2005...
Part no 089 152 Hot water control VST three way valve, DN 32 (1 ”) (Max recommended charge power, 40 kW) Part no 089 388 Double-jacketed hot water cylinder VPA 300/200 Part no 088 141 VPA 450/150 Part no 088 153 FIGHTER 2005...
For the Installer Technical specifications IP 24 FIGHTER 2005 -8 FIGHTER 2005 -11 Delivered/Supplied power* at 2/35 °C ** (kW) 6,9/1,9 9,3/2,6 Delivered/Supplied power* at 7/35 °C ** (kW) 7,5/1,9 10,6/2,6 Delivered/Supplied power* at -7/45 °C ** (kW) 5,3/2,2 6,9/2,8 Delivered/Supplied power* at 0/45 °C **...
For the Installer Technical specifications Working area Water temp. °C Return temp Flow temp Outdoor air temp. °C During shorter time it is allowed to have lower working temperatures on the water side, e.g. during start up. FIGHTER 2005...