5.6
Connection to the condensate
trap
1
2
Legend
1
Acces plugs for cleaning purposes
2
Condensate drain connection
3
Condensate trap
Connect the flexible pipe to a discharge
system leading to the sewer in
compliance with the instructions below:
Use the condensate drain flexible
connection pipe supplied (2).
Ensure there is a conbinual fall of 2.5°
(44 mm/m).
Do not let the condensate drain flexible
connection fall into the trap.
Do not use copper pipes.
Important notice:
The float of the condensate trap also
ensures fume tightness. Therefore, it
is not necessary to add water in the
condensate trap.
3
5.7
Flue connection
Different flue outlet configurations can be
carried out.
Consult your supplier for more
information about the other possibilities
and associated accessories.
Warning! You can only use flue
accessories approved for the ISOTWIN
CONDENS.
Saunier Duval's horizontal flue
automatically provides a 3° angle that
enables the return of the condensates to
the appliance.
Whatever the kind of flue system
chosen, observe the minimum
distances indicated in the chart below
to position the flue terminals.
24