Vent Terminal Clearances - Intertek Jotul GF 400 DV Sebago Installation And Operation Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

Horizontal Termination Clearance
Figure 19. Vent Terminal Clearances per National Fuel Gas Code.
A = Clearance above grade, veranda, porch , deck, or balcony
: 12 inches (30 cm) minimum.
B = Clearance to window or door that may be opened:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensation
on the window.
C = Clearance to permanently closed window:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN
We recommend 12 in. minimum to prevent condensation
on the window.
D = Vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 2 feet (60 cm)
from the centerline of the terminal: 18 inches
(46 cm) minimum.
E = Clearance to unventilated soffit: 12 inches (46 cm)
minimum.
F = Clearance to outside corner: **Min. 9 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
G = Clearance to inside corner: ** Min. 6 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
H = *Not to be installed within 15 feet (4.5 m) above a me-
ter/regulator assembly within 3 feet (90 cm) horizontally
from the center-line of the regulator.
I = Clearance to service regulator vent outlet:
3 feet (91 cm) minimum.
J = Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance:
12 inches (30 cm) minimum.
K = Clearance to a mechanical air supply inlet:
**Min. 3 feet (91 cm) above if within 10 feet horizontally,
U.S. / *6 feet (1.83 m) minimum / CAN
L =
Clearance above paved sidewalk or a paved driveway
1
located on public property: 7 feet (2.1 m) min.
V
Vent Terminal
X
Air Supply
Terminals Prohibited in this Area
M = Clearance under veranda, porch, deck, or balcony:
12 inches (30 cm) minimum.
N = Clearance to propane tank relief valve and filler connection***:
5 feet (1.52 m) minimum to tanks not filled on site
10 feet (3.05 m) minimum to tanks filled on site from bulk truck
* In accordance with CSA B149 Installation Codes.
** In accordance with the current ANSI Z223.1/NFPA 54, National
Fuel Gas Code. Note: Local Codes and Regulations may require
different clearances.
*** In accordance with the current NFPA 58 Liquified Petroleum
Gas Code
A vent shall not terminate directly above a sidewalk or driveway
1
which is located between two single family dwellings and serves
both dwellings.
Only permitted if veranda, porch, deck, or balcony, is fully open
2
on a minimum of two sides beneath the floor.*
12 ”
305
mm
Figure 20. Termination Clearance to overhangs
137750_Rev_L 11.16.12
N
2
2 1/2”
64 mm
3”
76 mm
15