Horizontal Termination - Intertek Jotul GF 400 DV Sebago Installation And Operation Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

137750_Rev_L 11.16.12
Horizontal Termination
Any horizontal termination must fall within the shaded
portion of the vent window graph illustrated in figs. 9
or 11. For Snorkel Terminations, see below.
Any horizontal termination except a snorkel termina-
tion, must include:
1)
Minimum rise of 2 ft.
2)
Minimum horizontal run of 12 in. when vertical
run is less than 8 ft.
3)
Maximum rise of 35 ft.
4)
Maximum horizontal run of 27 ft.
5)
No more than four 45° or two 90° Elbows
Follow all termination clearance guidelines as specified
in fig. 19.
The horizontal termination cap must maintain a 3"
clearance to any overhead combustible projections
2 1/2" or less. It must also maintain 12" clearance from
projections exceeding 2 1/2". See fig. 20.
Wall Cut-out Opening: A minimum 10" X 10" (250 mm x
250 mm) square hole is required for proper pipe clear-
ances through a combustible wall. Use a listed wall
thimble for the wall penetration.
DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULA-
TION.
Any horizontal run of vent must have a 1/4" rise for ev-
ery foot of run toward the termination cap. NEVER AL-
LOW THE VENTING TO RUN DOWNWARD FROM STOVE
TO TERMINATION; DOWNWARD VENT RUNS TRAP HEAT
AND CAUSE HIGH TEMPERATURES TO DEVELOP WITHIN
THE VENT THAT COULD START A FIRE.
Install a Vinyl Siding Standoff between the vent termi-
nation and an exterior wall covered by vinyl siding ma-
terial to prevent potential heat damage to the siding.
Do not recess the termination cap into a wall or siding.
Snorkel Terminations
THE AIR INLET RESTRICTOR MUST BE SET FULLY OPEN
FOR ANY SNORKEL TERMINATION. See Fig. 6, pg. 9.
With a 14" Snorkel:
The horizontal run made directly off the rear of the
stove into a 14" snorkel cap should include no more
than a single 12" straight section as shown in fig. 17.
One 45° Elbow may be used for a corner installation as
shown in fig. 18.
With a 36" Snorkel:
The maximum horizontal run may be no more than
6 ft. (182 cm.)
14
24 in.
Snorkel
(305 mm)
Figure 16.
• Minimum vent for horizontal termination.
• 14" Maximum horizontal run directly off rear of stove
with 14" Snorkel termination.
Figure 17. Maximum Horizontal and Vertical Run with 36"
Snorkel Termination.
45° Elbow
Figure 18. Corner Installation with 14" Snorkel Termination.
12 in.
(305 mm)
C L
14"
355 mm
57"
Max.
(1448 mm)
12"
25 1/2 in.
Vent
Snorkel
Pipe or
(648 mm)
less
36 in.
Max.
Snorkel
6 ft.
(915 mm)
183 cm
Max. 14"
355 mm
See Note F
Fig. 20
12 in.
Straight Pipe
Wall Thimble
and Trim Collar