Co-linear Vent Installation
This appliance may be vented through a masonry or Class
A prefabricated chimney using a Co-linear Flexible Vent
system approved for use with a solid-fuel burning fire-
place. When installed in the manner described below, this
system can improve the performance of the appliance in
cold climate situations, as well as simplify the vent instal-
lation. See fig. 13.
These installation requirements must be followed:
1. Use the guidelines for Co-linear Vent Termination ap-
propriate for your gas type on pages 10 - 11.
1. Prior to the installation the chimney flue must be thor-
oughly cleaned and inspected by a qualified chimney
service person.
2. In a masonry chimney, a fireclay liner must be present
the entire length of the chimney.
3. Prefabricated chimneys must be UL 103 or ULC S-629
listed and have a minimum INSIDE diameter of 6
inches, (150 mm).
4. No appliance can be installed into a chimney flue serv-
ing any other appliance of any kind.
5. THE AIR INTAKE FLEX PIPE MUST EXTEND 6 FEET BE-
YOND THE DAMPER AREA OF THE FIREPLACE.
6. If the intake flex duct does not extend the full length
of the chimney and connect to both the unit and the
termination cap, A METAL BLOCK OFF PLATE MUST
BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT
PRIOR TO THE END OF THE INTAKE FLEX AND MUST
COMPLETELY SEAL THE CHIMNEY FLUE FROM THE
ROOM.
Consult with the local code authority having jurisdic-
tion before proceeding with this type of installation.
Refer to the vent manufacturer's instructions for
specific installation requirements.
WARNING: FAILURE TO POSITION THE PARTS AND
STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE MAY RESULT IN PROPERTY
DAMAGE OR PERSONAL INJURY. BE SURE TO MAINTAIN
THE PROPER CLEARANCES TO COMBUSTIBLES AS DEFINED
IN THIS MANUAL AND IN THE INSTRUCTIONS PROVIDED
WITH EACH VENT COMPONENT.
12
Exhaust Gas
Max. Co-linear
Height - 35 ft.
(10.66 m)
Min. Co-linear
Height - 10 ft.
(3.05 m)
The chimney
must be sealed
off from the
room by a steel
plate at the
damper area.
Figure 13. Co-linear Adaptor installed through a masonry
chimney. Components shown may differ somewhat from
manufacturer to manufacturer.
Figure 14. Simpson Dura-Vent #923GCL Co-linear Adaptor
is shown - other manufacturer's components may differ.
Subtract 2 1/4" for Short Legs.
High Wind Cap
Intake Air
The Air
Intake Flex
pipe must
extend
beyond the
damper.
Dual 3"Flex
Liners
Max. offset
24"
(609 mm)
29"
to top of
Co-linear
25 1/2"
Adapter
to center
of flue collar