First startup of digital thermostats ......17 First setup of digital thermostats ......18 Installation report ..........38 Register thermostats to controller ......19 Finishing installation .........20 Operate Uponor Smatrix Space controller ..21 Principle of operation ..........21 Normal operation without optional scheduling programs ..............21 Operation with scheduling programs ......21 Run mode ...............21...
Modification or use of any of the contents of the The manual is provided “as is” without warranties of manual for any other purpose is a violation of Uponor’s any kind, either expressed or implied. The information copyright, trademark and other proprietary rights.
Risk of injury. Ignoring warnings can cause communication difficulties exist, Uponor recommends injury or damage components. relocating the controller to a more optimal position, and not installing Uponor radio sources to close to each other, for solving exceptional problems. Caution! Ignoring cautions can cause malfunctions.
An Uponor Smatrix Space system is the combination of a controller: • Uponor Smatrix Space Controller X-161 (controller) Together with one of the following thermostats: •...
The illustration below shows the controller with a through radio transmissions and are used individually. connected 2-way valve actuator (230 V). They all use the same type of battery. The following Uponor Smatrix thermostats can be used in the system: • Uponor Smatrix Wave Thermostat Standard T-165 •...
Page 7
Uponor Smatrix Wave Thermostat Standard T-165 Uponor Smatrix Wave Thermostat Dig T-166 The thermostat temperature settings are adjusted using The thermostat shows the ambient or set temperature the dial. The 21 °C position is marked on the dial. on the display. Temperature settings are adjusted using the +/- buttons on the front.
Room temperature regulation with use of optional Accessories external temperature sensors. • Displays optional temperature sensor values Uponor offers a wide variety of accessories for use with if sensors are connected and relevant room the standard portfolio. temperature regulation is activated. •...
Heating fall back If the connection to the thermostat is lost, the loop Uponor Smatrix Space is used to control a single zone in cannot be regulated using the air temperature. The an underfloor heating and/or cooling system in a house.
• Study the wiring diagram in the end of this manual. and sensors Finish installation To determine where to best place the Uponor Smatrix Space components, follow these guidelines: • Ensure that the controller can be installed close to the valve acutator. Note that each actuator must have its own controller.
Installation example Uponor Smatrix Space system A connection example of Uponor Smatrix Space Controller (single channel) using one of the thermostats as shown in figure. T-166 The installation will work in a standard way with the X-161 T-165 T-168 thermostat regulating the room according to its set temperature.
Install Uponor Smatrix Space controller Placement of controller Connect components to controller Refer to the installation preparation guidelines (see Refer to the wiring diagram found in the end of this section 4.2 Prepare for installation), and use the document. The illustration below shows the inside of following guidelines when positioning the controller: the controller.
Page 13
2A and 2B wireless radio link. on the controller. See also section 6 Uponor Smatrix Wave thermostats Heating/cooling output is now installed. and sensors for installation of thermostats. U P O N O R S M AT R I X S PA C E / S PA C E P L U S · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L...
1, on the controller shuts off, wait until fully closed. 3. Reset the setpoint to default values. The Uponor Smatrix Space controller is designed to be used with Uponor 230 V normally closed actuators. 230 V AC 50 Hz 3.
Install Uponor Smatrix Wave thermostats and sensors The following thermostats can be connected to the Insert batteries system: All thermostats use two alkaline 1.5 V AAA batteries • Uponor Smatrix Wave Thermostat Standard T-165 which provides about 2 years of battery life, as long as •...
Use the software on the thermostat to select a control mode which corresponds to the use of the sensor and thermostat. See section 10 Operate Uponor Smatrix Wave digital thermostats for more information. Uponor Smatrix Wave Thermostat Prog.+RH T-168...
At first startup, before registering, the thermostat the current values will be saved and the requires some basic settings. software exits to control mode. See section 10 Operate Uponor Smatrix Wave PLUS 1. Set hours. digital thermostats for more information. Software version Current software version is displayed during power up.
First setup of digital thermostats Temperature setpoint The thermostats are delivered with a default setpoint of Select thermostat control mode 21 °C (may differ depending on heating mode). If an external sensor is connected to the thermostat, The illustration below shows how to adjust the a control mode must be selected to accommodate the thermostat temperature setpoint.
Register thermostats to controller N O T E ! Repeating the registration process will The illustration below shows how to register one of the overwrite the old registration data. various room thermostats to the controller. To register a room thermostat to the controller: 1.
Finishing installation Make a complete check up of the installation: 1. Check that the thermostat is working correctly. Turn the thermostat setpoint to maximum to obtain a heating demand and make sure that the actuators are running. 2. Reset the thermostat to the defined operating settings.
Operate Uponor Smatrix Space controller Uponor Smatrix Space controls a single underfloor Run mode heating/cooling zone according to customer needs. The During normal operation the controller is in run mode. temperature is adjusted with a thermostat located in the room.
Two types of thermostats, both analogue and digital, Adjust temperature can be used in an Uponor Smatrix Space system. The temperature is changed by adjusting the setpoint on the thermostat to a value between 5 and 35 ˚C. Analogue thermostats: •...
Factory reset Factory reset sets all parameter values to default settings. N O T E ! Do not factory reset the thermostat if not absolutely needed. N O T E ! A factory reset removes the registration data from the thermostat. T-165 To factory reset an analogue thermostat: 1.
10 Operate Uponor Smatrix Wave digital thermostats Two types of thermostats, either an analogue or a 10.2 Display layout digital, can be used in an Uponor Smatrix Space system. The figure below shows all possible symbols and The digital thermostats have a display relaying characters that can be shown on the display: information to the user and buttons for control.
10.3 Operating buttons Pos. Icon Description The figure below shows buttons used to operate the Temperature unit, shown when the digital thermostats. character group A shows a temperature Communication indicator Indoor temperature indicator Remote sensor temperature indicator (RS mode) Indoor temperature with floor temperature limitation indicator Flashing floor sensor icon indicates a faulty sensor...
Set time and date (T-168 only) 7. Set year. When starting the thermostat for the first time, after a factory reset, or after its been left without batteries too long, the software requires the time and date to be set. Use buttons - or + to change the value, press the OK button to set the value and move to the next editable value.
10.7 Control mode 3. Use buttons - or + to change the numbers to 04 and press OK. The thermostat has four different control modes, set in 4. Current control mode is displayed (RT, RFT, RS or the settings menu. RO).
Page 28
00 Program (T-168 only) Program P4: In this menu, one of seven different scheduling programs for Comfort/ECO mode can be set. Program 1 to 6 is pre-programmed and the 7th is user programmable. Program Off (default): Zone is set in Comfort mode. If a timer is available in the system, the zone will use those set schedules but the thermostats own ECO mode setback temperature.
Page 29
Single day programming: 02 Heating/cooling changeover In this menu it is manually set whether the system is in 2.1.1 Use buttons - or + to select a day for heating or cooling mode. programming. To change this setting: 2.1.2 Press and hold the OK button until the hours appear.
Page 30
04 Control mode 06 Low floor temperature limitation In this menu control mode for the thermostat is set. In this menu a limit on the minimum allowable floor temperature is set. If an external sensor is connected to the thermostat, a control mode must be chosen to accommodate the extra This menu is only visible if control mode RFT is activated functionality of the sensor.
In this menu it is set whether the thermostat also should Factory reset sets all parameter values to default be integrated, and share temperature data, with an settings. Uponor Smatrix Move PLUS controller. N O T E ! Default value: no Do not factory reset the thermostat if not To change this setting: absolutely needed.
11 Maintenance The maintenance of Uponor Smatrix Space includes the The illustration below shows the position of the following: controller LEDs. • Manual preventive maintenance • Automatic preventive maintenance • Corrective maintenance • Controller LEDs 11.1 Manual preventive maintenance Uponor Smatrix Space requires no preventive maintenance except cleaning: 1.
12 Troubleshooting The table below shows problems and alarms that can occur with Uponor Smatrix Space and describes solutions. Problem Indication Probable cause Solutions Fluctuating floor Floor temperature is changing abnormally Supply water temperature is too high Check boiler or shunt...
12.1 Troubleshooting after installation Problem Indication Probable cause Solutions The controller does No LED indication on the controller when There is no AC power in the controller 1. Check that the controller is connected not start thermostat setpoint is changed to AC power The actuator never opens 2.
12.4 Controller alarms/problems An alarm is sent when more than 1 hour have elapsed since the controller received the last radio signal from the thermostat. The table below lists problems that can occur in the controller. Indication Probable cause Solutions Radio connection LED flashing rapidly The thermostat is out of radio range Reduce the distance between the thermostat and controller...
13 Technical data 13.1 Technical data General IP20 (IP: degree of inaccessibility to active parts of the product and degree of water) Max. ambient RH (relative humidity) 85% at 20 °C Max. radio distance between controller and thermostat 30 m Thermostat and timer CE marking Low voltage tests...
14 Installation report 230 V T-168 T-166 T-165 Controller Thermostat Rooms Thermostat Floor sensor Remote sensor Heating/cooling U P O N O R S M AT R I X S PA C E / S PA C E P L U S · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L...
Page 39
U P O N O R S M AT R I X S PA C E / S PA C E P L U S · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L...
Page 40
Uponor Corporation www.uponor.com Uponor reserves the right to make changes, without prior notification, to the specification of incorporated components in line with its policy of continuous improvement and development.