Section 5: Programming Sections

The structure of this section corresponds with the structure of the
Programming Worksheets (PWS) and is intended to be used with
them.

5.1 Keypad Programming

Refer to Section 2.7 'Keypad Assignment'

5.2 Basic Programming

[001]-[004] - Zone Definitions

These sections require 16 two-digit entries. Each two digit num-
ber entered determines how a zone will operate.
Option
Zone Type
00
Null Zone
01
Delay 1
02
Delay 2
03
Instant
04
Interior
05
Interior Stay/Away
06
Delay Stay/Away
07
Delayed 24-hr Fire
(Hardwired)
08
Standard 24-hr Fire
(Hardwired)
09
24-hr Supervisory
10
24-hr Supervisory
Buzzer
11
24-hr Burglary
12
24-hr Holdup
13
24-hr Gas
14
24-hr Heat
15
24-hr Medical
16
24-hr Panic
17
24-hr Emergency
18
24-hr Sprinkler
19
24-hr Water
20
24-hr Freeze
21
24-hr Latching Tamper
22
Momentary Keyswitch
Arm
Description
For zones that are not used and do not require a closed loop or EOL resistor
Follows the Entry Delay 1 and Exit Delay programmed in Section [005] and is normally used for Entry/Exit doors. The exit
delay starts as soon as the panel is armed. The zone may be opened and closed during the delay time without causing an
alarm. After the exit delay time has expired, opening the zone will start the Entry Delay timer. During the Entry Delay time,
the keypad buzzer will sound steadily to advise the user that the system should be disarmed. If the panel is disarmed before
the Entry Delay expires, no alarm will be generated.
Operates the same as Type [01] zone except the Entry Delay time can be independently set in Section [005]. The Exit Delay
time is common to both zone types.
Normally used for door and window contacts and has the standard Exit Delay, but is instant when opened after the Exit
Delay expires.
Used with interior motion detectors. Interior zones feature an Exit Delay and an Entry Delay provided that any Delay type
zone has been tripped first. If the protected area is entered without coming through the a delayed entrance and an Interior
zone is tripped, an immediate alarm will be generated.
If the system is armed and a Delay zone is NOT tripped during the exit delay time, this zone type will be bypassed. If the
[*][1] command is used to activate all Stay/Away type zones, this zone will have the standard exit delay. Once armed, this
zone will act like an Interior type zone [04].
If the system is armed and a Delay zone is NOT tripped during the exit delay time, this zone type will be bypassed. If the
[*][1] command is used to activate all Stay/Away type zones, this zone will have the standard exit delay. Once armed, this
zone will follow the Entry Delay time for Entry Delay 1 when tripped.
NOTE: The automatic bypass on Stay/Away type zones will not be removed by any event other than a valid exit
through a non-Global Delay type 1 zone during the exit delay or by pressing [*][1] while armed.
Operates the same as the standard Fire zone, except the alarm memory and transmission by the communicator is delayed by
30 seconds. If the alarm is acknowledged by pressing any key within 30 seconds, the bells will silence and the transmission
will be aborted. If the alarm has been acknowledged, and the smoke detector has not been restored to normal, the bell out-
put will activate after 90 seconds, the user then has another 30 second delay before the bell output latches and communi-
cations is activated. A code is then required to silence the bell output.
NOTE: The Fire Delay will be terminated if a 2nd Fire zone is tripped or if the [F] key is pressed during a delay.
This Fire Zone is used for pull station type circuits. On alarm, the bell output will sound to indicate that the fire loop has been
activated. If enabled, the communicator will immediately transmit the alarm to the monitoring station.
NOTE: DO NOT change the Zone Attributes of Fire type zones from the default settings.
This zone is active at all times and will report an alarm at all times. The supervision options (NC,EOL,DEOL) do not affect the
functionality of the zone. The restored state of this zone type is 5K6Ω the alarm state is short and the trouble state is open.
NOTE: This zone type must not be used for wireless zones
This zone is active at all times and will report an alarm at all times. Once tripped, the keypad buzzer will sound until a valid
access code is entered.
NOTE: This zone type should not be used on a Keyswitch ONLY system
This zone is active at all times and will report an alarm if the panel is armed or disarmed. This zone will sound the bell for the
length of 'Bell cutoff' if the audible attribute is enabled.
Similar to 24 Hour Burglary except for System Event output type and SIA identifier.
Similar to 24 Hour Burglary except for System Event output type and SIA identifier
Similar to 24 Hour Burglary except for System Event output type and SIA identifier.
Similar to 24 Hour Burglary except for System Event output type and SIA identifier
Similar to 24 Hour Burglary except for System Event output type and SIA identifier.
Similar to 24 Hour Burglary except for System Event output type and SIA identifier
Similar to 24 Hour Burglary except for System Event output type and SIA identifier
Similar to 24 Hour Burglary except for System Event output type and SIA identifier
Similar to 24 Hour Burglary except for System Event output type and SIA identifier.
This zone type, when violated, will cause arming of the system to be inhibited until the valid Installer code is entered. If this
zone type is violated, the Installers code must be entered ([*][8] Installers Code) before the system can be armed.
A keyswitch module may be connected to the zone programmed as Momentary Keyswitch arm. Momentary activation of
this zone to the alarm state will alternatively arm and disarm the system and silence alarms. Tampers and Faults will only ini-
tiate their respective trouble sequence.
NOTE:
In addition to selecting how each zone will operate,
attributes may be programmed by zone (see section 5.3 'Advanced
Programming' [101]-[164]).
19