Assembling The Boiler Block; Arrangement Of Boiler Sections - Buderus Logano GE615 Installation And Maintenance Instructions Manual

Calorific value forced draft sectional boiler
Hide thumbs Also See for Logano GE615:
Table of Contents

Advertisement

4
Installation
4.4

Assembling the boiler block

A distinction is made between delivery as a pre-
assembled block and delivery in loose sections. When
delivered as a block, the boiler sections are already fully
assembled and checked for leaks prior to despatch. If,
because of physical limitations, a boiler block cannot be
installed or brought inside the building, delivery in loose
sections would facilitate assembly on site.
The following describes the assembly of the boiler block
when delivered in loose sections.
For the further installation of a pre-assembled boiler
block, Æ see section 4.5, page 19.
4.4.1

Arrangement of boiler sections

Caution: Risk of injury
through inadequately secured boiler
sections.
z Use only suitable means of transportation
when handling the boiler sections, e.g. a
sack truck with strap or a stair or step
trolley.
z Prevent the boiler sections from sliding off
when transporting them.
V Prevent the boiler sections from falling
over using the installation aid (accessory)
First screw the rear section firmly onto the
installation aid (Æ Fig. 7).
The boiler block is always installed from the back for-
wards, i.e. the rear section (Æ Fig. 6, 3) is always installed
first, and the front section (Æ Fig. 6, 8) always installed
last.
When assembling, observe the installation direction
arrows (Æ Fig. 6, 7) for each boiler section.
Make sure you position the middle section with the upper
flow connection (Æ Fig. 6, 4) correctly!
Install the boiler block according to the following
instructions and illustrations.
The installation aid is available on request.
12
Fig 6
1
2
3
4
5
6
7
8
9
Fig 7
Logano GE615 - We reserve the right to make any changes due to technical modifications.
Assembled boiler block
Base/sound-absorbing boiler plinth
Flue gas header
Rear section
Central section with flow connection
Centre section
Anchor rod
Installation direction arrow
Front section
Burner door with burner plate
Rear section with fitted installation set

Hide quick links: