Troubleshooting A Ups Equipped With The Hotswap Mbp Module; Battery-Module Replacement; Safety Recommendations; Battery-Module Removal - MGE UPS Systems 2200 RT 2U Installation And User Manual

Mge ups systems installation and user manual pulsar m 2200 rt 2u, 2200 rt 3u, 3000 rt 2u, 3000 rt 3u, 3000 rt 3u xl, exb rt 3u
Hide thumbs Also See for 2200 RT 2U:
Table of Contents

Advertisement

Troubleshooting a UPS equipped with the HotSwap MBP module

10
11
12
If a fault leads to UPS shutdown, press the ON/OFF button (27) to clear the fault.

5.2 Battery-module replacement

Safety recommendations

The battery can cause electrocution and high short-circuit currents. The following safety cautions are required
before servicing the battery components:
Remove watches, rings, bracelets and all other metal objects from the hands and arms,
Use tools with an insulated handle.

Battery-module removal

Indication
The load is no longer supplied when
the rotary switch (49) on the HotSwap
MBP module is set to the Bypass
position.
The load is no longer supplied when
the rotary switch (49) on the HotSwap
MBP module is set to the Normal
position.
The load is no longer supplied if AC-
power fails.
Diagnostic
The protected devices are
connected to the UPS output
instead of to the HotSwap MBP
module.
The AC-power cord is connected
to the UPS input instead of to the
HotSwap MBP module.
The UPS is shut down.
The wiring between the UPS and
the HotSwap MBP module is not
correct.
The rotary switch (49) on the
HotSwap MBP module is set to the
Bypass position.
The wiring between the UPS and
the HotSwap MBP module is not
correct.
A - Unscrew the left-hand side of the front
panel (two screws).
B - Remove the part.
C - Disconnect the battery block by
separating the two connectors (never pull on
the wires).
5. Maintenance
Correction
Check the wiring between the UPS
and the HotSwap MBP module (see
section 2.6).
Start the UPS.
Check the wiring between the UPS
and the HotSwap MBP module (see
section 2.6).
Set the rotary switch (49) on the
HotSwap MBP module to the
Normal position.
Check the wiring between the UPS
and the HotSwap MBP module (see
section 2.6).
- Page 19
34007776EN/AB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents