Class 5 Status Codes - Fronius Galvo 1.5-1 Operating Instructions Manual

Operating instructions for inverter
Table of Contents

Advertisement

Available languages

Available languages

Code
Description
Fixed voltage mode has been
selected instead of MPP volt-
412
age mode and the fixed volt-
age has been set to too low or
too high a value.
Safety cut-out via option card
415
or RECERBO has triggered
No communication possible
416
between power stage set and
control system.
No communication possible
425
with the power stage set
445
Invalid limit value settings
Communication error between
452
the processors
453
Short-term grid voltage error
454
Short-term grid frequency error
457
Grid relay sticking
Error when recording the
459
measuring signal for the insu-
lation test
Reference voltage source for
the digital signal processor
460
(DSP) is working out of toler-
ance
Fuse for solar module ground
472
is faulty
Solar module ground, insula-
475
tion fault (connection between
solar module and ground)
482
Start-up incomplete
Class 5 status
Class 5 status codes do not generally prevent the feeding of energy into the grid, but can
codes
restrict it. These status code are displayed until they are acknowledged by pressing a key
(the inverter, however, continues to operate normally in the background).
Behaviour
-
The inverter is not feeding any
energy into the grid.
The inverter will automatically
attempt to connect again and,
if possible, will resume feeding
energy into the grid
The inverter is not feeding any
energy into the grid for safety
reasons.
The inverter will automatically
attempt to connect again and,
if possible, will resume feeding
energy into the grid
The inverter is not feeding any
energy into the grid.
The inverter is not feeding any
energy into the grid.
The inverter is not feeding any
energy into the grid.
The inverter is not feeding any
energy into the grid.
Remedy
If this status code keeps recur-
ring, contact your system engi-
neer
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
Update the inverter firmware;
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
notify a Fronius-trained service
engineer
Replace fuse for solar module
ground;
if this status code keeps recur-
ring, contact your system engi-
neer
If this status code keeps recur-
ring, contact your system engi-
neer
Perform AC reset (turn auto-
matic circuit breaker off and
on), complete start-up
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Galvo 3.0-1Galvo 2.0-1Galvo 2.5-1Galvo 3.1-1

Table of Contents