PHYSICAL REQUIREMENTS

Caution: Ensure that no water sources are above or near Powerwall, including downspouts,
sprinklers, or faucets.
Caution: Ensure that snow does not accumulate on top of or around Powerwall.
Caution: When installing Powerwall in a garage or near vehicles, keep it out of the driving
path. If possible, install the Powerwall on a side wall and/or above the height of vehicle
bumpers.
Caution: Powerwall has a pre-installed aesthetic front cover. To prevent damage, keep
Powerwall flat on its back until just before lifting Powerwall onto the wall mount bracket.
Powerwall must be installed on upright walls that can support 115 kg (254 lbs), the maximum
weight of Powerwall and its installation packaging. Do not mount Powerwall horizontally or upside
down. Do not mount Powerwall on a wall that is tilted backward or forward more than 5 degrees.
Powerwall requires adequate clearance for installation, cabling, and airflow. Do not mount any
other objects within the clearance space illustrated below, except those explicitly required by the
installation (for example, conduit or DC disconnect depending on local installation codes). Do not
install anything between Powerwall and the ceiling.
Powerwall is capable of charging and discharging within the full ambient temperature range listed
in the Specifications section. At the high and low ends of the temperature range, Powerwall may
limit charge or discharge power based on battery cell temperature to improve battery lifespan.
Installation in full sun raises the temperature inside the enclosure above ambient temperature. This
temperature rise is not a safety risk, but can impact the performance of the batteries. Installation
in full sun is not recommended to optimize the use of Powerwall.
Do not install Powerwall in a room with sustained elevated temperatures, such as a boiler room.
The average ambient temperature over the system's life should be 30°C (86 °F) or less.

NON-PHYSICAL REQUIREMENTS

Powerwall must be installed with a compatible inverter. Wiring and conduit (where necessary)
must be provided by the installer.
DC disconnect requirements between Powerwall and the inverter are subject to local codes.
Ensure that the installation meets local DC disconnect requirements. Check the inverter
installation manual to understand site connections and overcurrent protection.
All U.S. and Canada electrical installations must be done in accordance with local codes and the
National Electric Code (NEC) ANSI/NFPA 70 or the Canadian Electrical Code CSA C22.1.
All installations must conform to the laws, regulations, codes, and standards applicable in the
jurisdiction of installation.