3.5

Power Supply and Wiring

CP450 must use the power supply with 24 V DC and the power consumption
is 30W.
Warning:
To avoid an electrical shock, be sure to switch off the power before connecting the
communication/download cable to the operator terminal.
Perform the following steps to wire the power connector:
1. Unplug the power connector and unscrew the screws.
2. Strip approximately 7-8 mm of insulation. Insert the wire all the way into
the power connector and then turn the screws tight.
3. Plug in the connector to the power input of the operator terminal
Note:
The power connector is already plugged into the power input of operator terminal
when the package is first opened.
Type
Solid
Stranded
Use copper conductors only, 60/75
12
Wire Gauge
(AWG)
28-12
30-12
°
C.
Stripped Length
7-8 mm
7-8 mm
ABB, 1SBC159105M0202
Torque
4.5 lb-in
4.5 lb-in