Manitowoc Indigo Series Technician's Handbook page 132

Air/water/remote condenser ice machines
Hide thumbs Also See for Indigo Series:
Table of Contents

Advertisement

Operational Analysis
Discharge Line
Temperature
Record freeze cycle
discharge line temperature at
the end of the freeze cycle
_________°F (°C)
Final Analysis
Enter total number of boxes
checked in each column.
SINGLE EVAPORATOR, DUAL EXPANSION VALVE
SELF CONTAINED AIR, WATER & REMOTE CONDENSER
1
Discharge line temp.
150°F (65°C)
or higher at the end of
the freeze cycle
Harvest Valve
Leaking
2
Discharge line temp.
Discharge line temp.
150°F (65°C)
or higher at the end of
150°F (65°C) at the end
the freeze cycle
of the freeze cycle
Low On Charge
-Or-
TXV Starving
3
Discharge line temp.
less than
150°F (65°C) or higher
at the end of the
freeze cycle
TXV Flooding
Compressor
4