Operational Analysis
Freeze Cycle
Discharge Pressure
_______
______
______
1 minute
Middle
End
into cycle
Freeze Cycle
Suction Pressure
_______
______
_____
1 minute
Middle
End
Wait 5 minutes into the
freeze cycle.
Compare temperatures of
compressor discharge line
and both harvest valve
inlets.
SINGLE EVAPORATOR, DUAL EXPANSION VALVE
SELF CONTAINED AIR, WATER & REMOTE CONDENSER
1
If discharge pressure is High or Low refer to freeze cycle high or low discharge pressure problem checklist
page 140 to eliminate problems and/or components not listed on this table before proceeding.
If suction pressure is High or Low refer to freeze cycle high or low suction pressure problem checklist
page 144 to eliminate problems and/or components not listed on this table before proceeding.
Suction pressure is High
The harvest valve inlet is
Hot
-and-
approaches the
temperature of a Hot
compressor discharge
line.
2
Suction pressure is Low
or Normal
The harvest valve inlet
The harvest valve inlet
is Cool enough to hold
is Cool enough to hold
hand on
-and-
the compressor
discharge line is Hot.
discharge line is Cool
enough to hold hand on.
3
Suction pressure is
Suction pressure is
High
The harvest valve inlet
is Cool enough to hold
hand on
-and-
the compressor
the compressor
discharge line is Hot.
4
High
hand on
-and-