Entrapment Adjustment
Changes sensitivity of the inherent entrapment system from off, 0-99. Increase value
until gate runs smoothly without false entrapment. 0 is the most sensitive and 99 is the
least sensitive. Set a nominal entrapment level of 25.
No Position or Speed
Verify with the Troubleshooting Screen (see page 19).
WARNING
Do not run system without hall sense (speed sense) for more than 1 minute, as
overheating will occur.
1
Check sensor harness for connection and security (see Figure 22).
2
Adjust sensor by loosening bracket screws and inserting sensor until it barely
touches the target disk inside the motor.
3
If motor continues to surge or not run, adjust sensor again.