Troubleshooting - Emerson Network Poewr MPH2 User Manual

Rack pdu
Hide thumbs Also See for Network Poewr MPH2:
Table of Contents

Advertisement

5.0
T
ROUBLESHOOTING
LED Indication
(One or All LED's)
State/Flash
Color
Speed
Green
Fast
Green
Steady On
Off
NA
Red
Steady On
Red
Fast
Green
Slow
Red
Fast
Red
(All Receptacle
Pulse
LED's)
Green
(All Receptacle
Slow
LED's)
Red
(All Receptacle
Fast
LED's)
®
Emerson
MPH2
Audible
Alarm
Condition
Receptacle
Identification
Input Voltage Supported
Receptacle Powered On
Voltage Off
Line Undervoltage
Alarm
Line or Receptacle
Overcurrent Alarm
Line or Receptacle
Overcurrent Warning
Line or Receptacle
Undercurrent Alarm
Branch Circuit
Breaker Open
Branch Overcurrent
Warning
Branch Overcurrent
Alarm
30
Status/Recommended Action
Remote user is requesting outlet identification.
The LED should stop flashing after 10 seconds.
Normal Operation
Check power source and input plug's receptacle
wiring.
Check receptacle power control settings.
Check power source for power quality problem. If
the MPH2 uses 3-phase power, a single low-
voltage phase may cause one or more
undervoltage alarms. The undervoltage alarm is
factory-set to -10% of the minimum input voltage
range on the nameplate; it cannot be changed.
Check for changing load conditions.
Check overcurrent alarm threshold settings.
Check for changing load conditions.
Check overcurrent warning threshold settings.
Check for removal of load.
Check undercurrent alarm threshold settings.
Check for changing load conditions; confirm circuit
breaker actuator is closed. If open, correct loading
condition before pressing circuit breaker actuator
closed again.
Check for changing load conditions.
Check overcurrent warning threshold settings.
Check for changing load conditions.
Check overcurrent alarm threshold settings.

Troubleshooting