Table 1
Hard-wired models—Connection terminal ratings
Conductor Cross-Section Solid, Minimum
Conductor Cross-Section Solid, Maximum
Conductor Cross-Section Stranded, Minimum
Conductor Cross-Section Stranded, Maximum
Conductor Cross-Section, AWG/kcmil, Minimum
Conductor Cross-Section, AWG/kcmil, Maximum
Conductor Cross-Section Stranded, With Ferrule
Without Plastic Sleeve, Minimum
Conductor Cross-Section Stranded, With Ferrule
Without Plastic Sleeve, Maximum
Conductor Cross-Section Stranded, With Ferrule
With Plastic Sleeve, Minimum
Conductor Cross-Section Stranded, With Ferrule
With Plastic Sleeve, Maximum
Table 2
Terminal tightening torque
Tightening Torque
Minimum
Maximum
2.2
Tool-less Mounting
For tool-less mounting, attach the mounts to the rear of the MPH2 rack PDU, then hang it in the rack
as shown in Figure 10. Torque the screw attaching the mounting button 17 lb-in (2Nm).
NOTE
Brackets are not supplied. A range of brackets for Emerson and other manufacturers' racks are
available as accessories.
Figure 10 Tool-less mounting
Button Mount
Torque screw
17 lb-in (2Nm)
®
™
Emerson
MPH2
0.2mm
0.2mm
0.25mm
0.25mm
MPH2 Rating
≤32A
>32A
0.6 Nm
1.5Nm
0.8Nm
1.8Nm
12
MPH2 Rating
≤32A
>32A
²
²
0.5mm
²
²
6mm
16mm
²
²
0.5mm
²
4mm²
10mm
24
20
10
6
²
²
0.5mm
²
²
4mm
10mm
²
²
²
0.5mm
²
²
4mm
10mm
Insert the Button Mount
into the Keyhole Slot
Installation