Hard-Wired Connection Features; Figure 6 Circuit Breaker Branch Identification - Emerson Network Poewr MPH2 User Manual

Rack pdu
Hide thumbs Also See for Network Poewr MPH2:
Table of Contents

Advertisement

Branch Overcurrent Protection
Models having more than 16A input current rating are equipped with branch overcurrent protection.
This protects each outlet group against overload and short circuit. The branch circuit breaker is a
UL 489-listed breaker with a flush-mount, rocker-style actuator. The circuit breaker interrupts the
fault current flowing in the line-to-line, line-to-neutral and line-to-PE conductors of the branch
circuits. The branch circuit breaker ratings apply over the full rated operating temperature and
frequency.
The flush-mount breakers guard against accidental trips that could interrupt power to the connected
load. Manually tripping a breaker requires a small, flat blade, such as a screw driver (see Figure 29).
Low-profile circuit breakers are used on all MPH2 rack PDU's with two or three branch circuits less
than 240V rating in a line-neutral configuration. Standard-profile circuit breakers are used on MPH2
rack PDU's with six branch circuits or have a 240VAC rating. Each type of circuit breaker is a rocker
style (see Figure 29).
The branch circuit breaker labeling (A, B, C and so on) shows which outlets are protected by each
specific breaker. Outlets on Branch A are protected by the circuit breaker labeled A. Three-phase
PDU's may also have labeling showing the phase associated with each circuit breaker.
NOTE
The branch circuit breaker is not designed to be used as a disconnect device for the connected
load.
Figure 6
Circuit breaker branch identification
Branch Identification
Branch Circuit Breakers
1.3.5

Hard-Wired Connection Features

Emerson's MPH2 rack PDU may be equipped with either a factory-installed input power cord or
hard-wired connections. The hard-wired connection will be at one end of the unit. A terminal block in
the hard-wired connection compartment is coded to aid in making the connections. A collar secures
the input wire, keeping the strain off the terminal block connections. See Figure 7.
®
Emerson
MPH2
Standard Profile
Branch Identification
Branch Circuit Breakers
Low Profile
8
Introduction

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents