4.0
E
MPH2 R
MERSON
Input Power Configurations; Vary by Model and Region
Single-Phase Input; CE-Mark
240VAC, 16A; also UL-listed
Three-Phase Input; CE-Mark
Single-Phase Input; UL-Listed
Three-Phase Input; UL-Listed
120/208VAC 48A; 240/415VAC, 24A
Input Wiring Options
Outlet Options
Number of Outlets, Maximum
Power Consumption, Maximum
Measurement Accuracy
Insulation
Dielectric Electric Strength
Overcurrent Protection
Operating Temperature Range, °F (°C)
Storage Temperature Range, °F (°C)
Humidity, %
Altitude, ft. (m)
Mounting
Zero-U Units, Width x Depth, in. (mm)
Zero-U Units, Length, in. (mm)
Safety Standards
(Vary by Model and Region)
EMC Standards
(Vary by Model and Region)
Agency Approvals
(Vary by Model and Region)
PDU S
ACK
3.7kW
230V, 32A
7.3kW
230/400V, 16A
11kW
230/400V, 32A
22kW
120VAC 16A
1.9kW
120VAC 24A
2.9kW
208VAC 24A
4.9kW
120/208VAC, 24A
8.6kW
120/208VAC, 40A
14.4kW
17.3kW
40A and 48A Input Models without case ventilation: 32 to 122 (0 to 50)
40A and 48A Input Models with case ventilation: 32 to 140 (0 to 60)
Emerson
PECIFICATIONS
8 to 10 ft. (2.4 to 3m) Non-Detachable Power Supply Cord
Hard-Wired Terminal Block
NEMA 5-15; NEMA 5-20; IEC 320C13; IEC 320 C19
Voltage: ±1% +0.1VAC
Current: ±1.5% + 0.01A from 1% to 10% of unit rating;
±1% +0.01A from >10% to 125% of unit rating
Class I, Reinforced SELV
Tested up to 4242VDC
UL489-Listed, CSA, TUV, CCC Overcurrent Circuit Breaker,
20A, 5000A A.I.C
32A or Less Input Models: 32 to 140 (0 to 60)
-13 to 185 (-25 to 85)
10 to 90 non-condensing
6562 (2000)
Factory-Installed Toolless Brackets
Universal Mounting Bracket
Low-profile: 2.2 x 1.96 (56x50)
Standard: 2.2 x 2.7 (56 x 70)
13.1 - 72.2 (333 - 1833)
IEC 60950-1:2005 (Second Edition) + Amendment 1:2009
CSA C22.2 NO. 60950-1-07 (2nd Edition) + Amendment 1:2009
UL 60950-1 (2nd Edition) + Amendment 1:2009
IECEE CB Full Certification Scheme
FCC Class A, Part 15, Industrial
EN55022:2006+A1:2007, Class A, Industrial
EN55024:1998+A1:2001+A2:2003, Class A, Industrial
IEC61000-3-2:2006, IEC61000-3-3:1995+A1:2001+A1:2005
IEC61000-4-2/3/4/5/6/8/11
UL, cUL, CE, BV, CB, RoHS, REACH, WEEE
29
®