Vitocal 300-A/350-A
Required parameter settings
ID: 4605093_1304_05
Vitotronic 200, type WO1B
Parameter
7000
71FE
7100
7101
7103
7A00
3003
ID: 4605093_1304_05
Vitosolic 100, type SD1
Parameter
ANL
"RPM"
System examples
(cont.)
Value
Function
10
With heating circuit A1/HC1, M2/HC2, M3/HC3, DHW cylinder
1
Enable active cooling
3
Active cooling
2
Cooling on heating circuit M2/HC2
180
Min. flow temperature, cooling
1
With Vitosolic 100, type SD1
1
Vitotrol 200A remote control activated for heating circuit M2/HC2
Value
Function
2
System version
"0"
Pump with electronic speed control (delivered condition)
"1"
Standard solar circuit pump without separate variable speed control - speed controlled by
pulse pack control
"2"
Pump with PWM input (Wilo)
"3"
Pump with PWM input (Grundfos)
7
VIESMANN