Download Print this page

Viessmann Vitocal 222-G User Manual page 190

Advertisement

Vitocal 200-A
(cont.)
Required parameter settings
ID: 4605507_1304_02
Vitotronic 200, type WO1C
Parameter
2003
3003
7000
7008
7010
701B
7100
7101
7103
7B00
7B0D
6014
Vitotronic 200, type KO1B, KO2B, KW6B
Group
"General"
"General"
"General"
System examples
Value
Function
1
Enable remote control for heating circuit A1/HC1
1
Enable remote control for heating circuit M2/HC2
6
With heating circuit A1/HC1, M2/HC2, DHW cylinder, heating water buffer cylinder
1
Enable swimming pool heating
1
External extension
1
Common system flow temperature sensor is activated
3
Enable active cooling function
2
Cooling via heating circuit M2/HC2
180
Min. flow temperature, cooling
1
Enable external heat source for central heating
1
Enable external heat source for DHW heating
1
Immersion heater or external heat source is enabled for DHW reheating
Code
Function
3A : 3
Function input DE1 at EA1 extension: External blocking
3b : 2
Function input DE2 at EA1 extension: External demand
9b : 70
Set value for external demand (delivered condition)
6