Programming Menus - Bunn AutoPOD Technical Training Manual

Table of Contents

Advertisement

Programming Menus

BREW LOCKOUT ?
NO
DONE
YES
BREW TYPE A
TEA
DONE
COFFEE
BREW OZ A: 8.0
(-)
DONE
(+)
BREW METER A:
3
-
+
ENTER SERVICE #?
NO
YES
ENTER PASSWORD
0
0
0
SET PASSWORD
0
0
0
SET LANGUAGE ?
NO
YES
UNITS
METRIC
DONE
ENG
SET TEMP:
200
O
(-)
DONE
(+)
SET READY:
195
O
(-)
DONE
(+)
HOT H2O LOCKOUT ?
NO
DONE
YES
HOT H2O TEMP: 200
O
(-)
DONE
(+)
H2O READY: 195
O
(-)
DONE
(+)
8
AutoPOD™ Training Manual
Brew Lockout
Prevents brewing if the water temperature is less than the "SET READY" temperature.
Brew Type (A/B) (Tea/Coffee)
Tea setting provides half the "purge" pressure as coffee at the end of brew cycle.
Brew Oz (A/B) (1-16 oz.)
Adjust brew volume.
Brew Meter (A/B) (1-5)
Simplified pulse brew adjustment. 1=Preinfusion, 2-5=Pulse brew. 2 being the shortest
pulse brew cycle and 5 being the longest.
Enter Service #
Program service phone number to be displayed anytime there is a fault message.
Enter Password
User must enter a 3 digit password to access remainder of adjustments. If no number
has been pre-programmed (000), then access is allowed.
Set Password (001-999)
Program any 3 digit number as a password.
Set Language
Chose between English and Spanish.
Units
Chose between English (Oz, ºF) or Metric (Ml, ºC).
Set Temp
Adjust tank temperature 185º F to 200º F (85º C to 96º C).
Set Ready
Sets the minimum temperature allowable to start a brew cycle. If BREW LOCKOUT is en
abled. Range: (2º F to 20º F) or (2º C to 10º C) below the set temperature.
Hot H2O Lockout
Prevents a hot water dispense if water is not up to the H2O Ready temperature, if
enabled.
Hot H2O Temp
Adjust tank temperature 185º F to 200º F (85º C to 96º C).
H2O Ready
Sets the minimum temperature allowable to start a hot water dispense.