APPLICABLE CONTROLS

NOTIFICATION
When using the equipment at the first time, it will take a lot of time that the remote controller accepts an
operation after power was on. However, it is not a trouble.
• Automatic address
• While automatic addressing, the operation cannot be performed on the remote controller.
• For automatic addressing, Max. 10 minutes (generally, approx. 5 minutes) are required.
• When power will be turned on after finish of automatic addressing;
• It will require Max. 10 minutes (generally, approx. 3 minutes) that outdoor unit starts operation after power
was on.
As all have been set to [Standard] at the shipment, change the setup of the indoor unit if necessary.
To change the setup, use the main remote controller (wired remote controller).
* The setup change for wireless remote controller, sub remote controller, or remote controller-less system
(Central control remote controller only is provided.) is impossible. In these cases, prepare and mount a
separate main remote controller.
Exchange of applicable control setup
Basic operation procedure for setup exchange
Change the setup while operation of the equipment stops.
(Be sure to stop the operation of a set.)
Procedure
SET
CL
TEST
When pushing
,
, and
buttons simultaneously for 4 seconds or more, after a while, the display part
flashes as shown in the figure.
Check that the displayed item code is [10].
• If the item code indicates other than [10], push
1
the display, and then retry the operation from the first step.
TEST
(For some time after
button has been pushed, the operation of
the remote controller cannot be accepted.)
(In a group control, the firstly displayed
indoor unit No. becomes the header unit.)
UNIT
Every pushing
button, the indoor unit No. in the group control is displayed successively.
Select an indoor unit of which setup to be changed.
2
In this time, the position of the indoor unit of which setup to be changed can
be confirmed because the fan and the flap of the selected indoor unit work.
Using
,
buttons of set temperature, specify the item
3
**
code [
].
Using
,
buttons of timer time, select set data [
4
SET
Push
button. In this time, if the display changes from flashing to lighting, the setup completes.
• To change the setup of an indoor unit other than the selected one, start operation from Procedure
5
• To change the setup of another setup in the selected indoor unit, start operation from Procedure
CL
Pushing
button clears the set up contents which have been already set. In this case, retry from Procedure
TEST
When the setup finished, push
button. (The setup is determined.)
TEST
Pushing
button deletes the display and returns the status to
6
normal stop status.
TEST
(For some time after
button has been pushed, the operation of the
remote controller cannot be accepted.)
CODE No.
UNIT No.
R.C.
No.
TEMP.
ON / OFF
3
4
TIMER SET
FAN
MODE
2
1
TIME
SWING/FIX
VENT
FILTER
RESET TEST
SET CL
UNIT
6
5
Description
CODE No.
TEST
SETTING
button to erase
UNIT No.
R.C.
No.
(* The display changes according
to the indoor unit model.)
∗∗
CODE No.
∗∗ ∗
UNIT No.
∗ ∗∗
****
R.C.
No.
].
2
.
3
.
Setup of external static pressure
Be sure to set up a tap change based upon the
resistance (external static pressure) of the duct to be
connected.
To set up a tap change, follow to the basic operation
1
2
3
4
5
procedure (
• Specify [5d] to the item code in procedure
4
• For the setup data of procedure
, select a setup
data of the external static pressure to be set up from
the following table.
In case of remote controller-less (Group control)
For setup to the high ceiling, there is selecting method by exchanging the short plugs on the indoor microcomputer
P.C. board as shown in the following table other than selecting method by standard wired remote controller (sold
separately). Utilize this method for remote controller-less (Group control) case.
∗ However, when the setup to high ceiling has been once exchanged, it is required for returning it to 0000 to change
the short plug to the standard (at shipment) position and rewrite data to the setup data 0000 from the wired remote
controller sold separately though setup to 0001, 0003 or 0006 are freely available.
• Select by exchange of short plugs on the indoor
P.C. board.
Short plug position
Set data
External static pressure
Short
Open
CN112 CN111 CN110
0000
10 Pa (At shipment)
CN112 CN111 CN110
0001
20 Pa
CN112 CN111 CN110
0003
35 Pa
CN112 CN111 CN110
0006
50Pa
2
.
<Change on wired remote controller>
Setup data
External static pressure
0000
10 Pa
0001
20 Pa
6
).
0003
35 Pa
3
.
0006
50 Pa