3. Data display of outdoor cycle (Displayed on each outdoor unit)
SW01
SW02
SW03
1
1
2
Pd pressure data
2
Ps pressure data
3
PL pressure conversion data Estimated pressure of liquid line (MPaG) is displayed with decimal data.
4
TD1 sensor data
5
TD2 sensor data
6
TS1 sensor data
7
TS2 sensor data
8
TE sensor data
9
TL sensor data
10
TO sensor data
11
TK1 sensor data
12
TK2 sensor data
13
TK3 sensor data
14
TK4 sensor data
15
16
4. Data display of indoor unit information (Displayed on the header unit only)
SW01
SW02
SW03
4
1 to 16
1 to 3
Receiving status of
indoor BUS communication
5
Indoor check code
6
Indoor capacity
(HP) horse power
7
Indoor request command
(S code)
8
Indoor PMV opening data
9
Indoor TA sensor data
10
Indoor TF sensor data
11
Indoor TCJ sensor data
12
Indoor TC1 sensor data
13
Indoor TC2 sensor data
NOTE) Indoor address No. is chosen by changing SW02 and SW03.
SW03
SW02
Indoor address
1
1 to 16
SW02 setup number
2
1 to 16
SW02 setup number + 16
3
1 to 16
SW02 setup number + 32
Pd pressure (MPaG) is displayed with decimal data.
(MPaG: Approx. 1/10 value of kg/cm
Ps pressure (MPaG) is displayed with decimal data.
Temperature sensor data (°C) is displayed
with decimal notation.
• Symbol display for 1 sec. and data display for 3 sec. are
alternately displayed.
• Data is displayed in [∗].
• Negative data is displayed as [– ∗ ∗ ∗ ∗].
A
B
A
B
Receiving time: [ ... ... 1], Not received: [ ... ... ... ]
B
B
No check code: [– – –]
0. 2, 0. 5, 0. 8, ... 1, 1. 2, 1. 7, ... 2, 2. 5, ... 3, 3. 2, ... 4, ... 5,
B
... 6, ... 8, 1 0, 1 6, 2 0
Data is displayed with Hexadecimal notation [ ... ... 0 to ... ... F] : Heating
B
B
Data is displayed with Hexadecimal notation
B
Data is displayed with Hexadecimal notation
B
Data is displayed with Hexadecimal notation
B
Data is displayed with Hexadecimal notation
B
Data is displayed with Hexadecimal notation
B
Data is displayed with Hexadecimal notation
7-segment display A
[01] to [16]
[17] to [32]
[33] to [48]
Display contents
2
G data)
Display contents
111
P d.
P S.
P L.
Symbol
t d
Data
Symbol
t d
Data
Symbol
t S
Data
Symbol
tS
Data
Symbol
tE
Data
Symbol
t L
Data
Symbol
t o
Data
Symbol
F 1
Data
Symbol
F 2
Data
Symbol
F 3
Data
Symbol
F 4
Data
A
B
∗. ∗ ∗
∗. ∗ ∗
∗. ∗ ∗
1
1 1
∗ ∗. ∗
2
1 1
∗ ∗. ∗
1
1 1
∗ ∗. ∗
2
1 1
∗ ∗. ∗
∗ ∗. ∗
∗ ∗. ∗
∗ ∗. ∗
∗ ∗. ∗
∗ ∗. ∗
∗ ∗. ∗