Toshiba MMD-AP0071SH-C Service Manual page 119

Table of Contents

Advertisement

No.
Part name
ƒ
E-cover
1. Detachment
2. Attachment
NOTE)
Be sure not to catch TA sensor in the E-cover;
otherwise the equipment cannot operate cor-
rectly.
NOTE)
If there is clearance, dust may enter in the
electric parts box.
E-box
1. Detachment
2. Attachment
NOTE)
Be sure to fix surely as before the lead wires of
which clamps and tie wrap were taken off.
NOTE)
Check that lead wires of the drain pump do not
reach the fan so that they are not caught in the
fan, and then fix them.
(In case of drain pump incorporated model)
Procedure
1) Perform work 1. of
.
2) Take off screws fixing E-cover, and then
remove hooks of the hooking part by lifting
up. (Ø4 × 10, 2 pcs)
1) Hang on E-cover to hooks of the hooking
part so that it does not fall down.
2) Using the screws taken off in procedure 1.
ƒ
2) of
, attach E-cover while holding it
with hands without clearance.
1) Perform works 1. of
2) Remove clamps and tie wrap at upper part
of the photo.
(Drain pump incorporated model:
3 positions)
(Natural drain model: 2 positions)
3) Take off screws fixing E-box.
(Ø4 × 10, 2 pcs)
E-box does not fall down under condition
that screws are taken off.
4) Remove the E-box over sheeting metal
which was fixed with screws.
1) Insert hooks of E-box into the hooking part
of the main body.
2) Store E-box as before, and then attach it by
using screws taken off in procedure 1. 3) of
.
ƒ
and 1. of
.
Drain pump
Lead wire:
For only drain pump incorporated model
119
Remarks
2 screws
TA sensor
Hooking part
E-cover
E-cover
E-cover
Clamp
Tie wrap
Tie wrap
Tie wrap
2 screws
E-cover
E-cover
E-cover
Clamp

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents