Check code
Outdoor 7-segment display
Main
remote
controller Check code
Sub-code
H16
H16
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
L03
L04
L04
L05
Detected
Check code name
AI-NET
position
central control
remote controller
d7
I/F
Oil level detective circuit system error
MG-SW error
OCR operation
96
Indoor
Duplicated indoor center units
96
I/F
Duplicated outdoor line address
96
I/F
Duplicated indoor units with priority
(Displayed on indoor unit with priority)
Status
Error detection condition
All stop
Temperature change of TK1
• Check TK1 sensor coming-off.
could not be detected though
• Check characteristics of TK1 sensor resistance value.
compressor 1 started the
• Check TK1, TK2, TK3, and TK4 misconnection.
operation.
• Check operation error of SV3E valve.
• Check capillary clogging of oil-equation circuit and
• Check refrigerant stagnation in compressor.
• Check MG-SW or OCR.
Temperature change of TK2
• Check TK2 sensor coming-off.
could not be detected though
• Check characteristics of TK2 sensor resistance value.
compressor 2 started the
• Check TK1, TK2, TK3, and TK4 misconnection.
operation.
• Check SV3E valve operation.
• Check capillary clogging of oil equalization circuit and
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
Temperature change of TK3
• Check TK3 sensor coming-off.
could not be detected though
• Check characteristics of TK3 sensor resistance value.
compressor started the
• Check TK1, TK2, TK3, and TK4 misconnection.
operation.
• Check SV3E valve operation.
• Check capillary clogging of oil-equalization circuit and
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
Temperature change of TK4
• Check TK4 sensor coming-off.
could not be detected though
• Check characteristics of TK4 sensor resistance value.
compressor started the
• Check TK1, TK2, TK3, and TK4 misconnection.
operation, or the difference
• Check SV3E valve operation.
from other TK sensor
• Check capillary clogging of oil-equalization circuit and
changed for a constant time
only within the specified
range.
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
• Check indoor address.
Corresponding
There are multiple center
unit only stops.
units in a group.
• Check the change of remote controller connection
Line address setup is
• Check line address.
All stop
duplicated against the
outdoor unit in different
refrigerant pipe system.
All stop
Indoor units with priority were
• Check display of indoor unit with priority.
duplicated.
MG-SW : Magnet Switch, OCR : Over-current Relay
Check item (position)
operation error of stop valve.
check stop valve operation.
check valve operation.
check valve operation.
(Group/individual) after indoor address setup.