Toshiba MMD-AP0071SH-C Service Manual page 72

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
controller Check code
Sub-code
F13
F13
01: Compressor 1 side
02: Compressor 2 side
F15
F15
F16
F16
F23
F23
F24
F24
F29
F31
F31
H01
H01
01: Compressor 1 side
02: Compressor 2 side
H02
H02
01: Compressor 1 side
02: Compressor 2 side
(*1) All stop only in case of the header unit
Detected
Check code name
AI-NET
position
central control
remote controller
43
IPDU
TH sensor error
18
I/F
Outdoor temp sensor
miscabling (TE1, TL)
43
I/F
Outdoor pressure
sensor miscabling
(Pd, Ps)
43
I/F
Ps sensor error
43
I/F
Pd sensor error
12
Indoor
Indoor other error
1C
I/F
Outdoor EEPROM error
1F
IPDU
Compressor breakdown
1d
IPDU
Compressor error (lock)
MG-SW error
OCR operation
The follower unit continues operation.
Status
Error detection condition
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
All stop
During operation of
compressor in HEAT mode, the
TE1 detection temp was higher
than that of TL by the specified
value continued for 3 minutes
or more.
All stop
High-pressure Pd sensor and
low-pressure Ps sensor were
exchanged, or output voltages
of both sensors are zero.
All stop
Output voltage of Ps sensor
was zero.
All stop
Output voltage of Pd sensor
was zero. (Sensor Open)
Pd > 4.15MPa during stop of
compressor
Corresponding
Indoor P .C. board did not
unit only stops.
operate normally.
All stop (*1)
Outdoor P .C. board (I/F) did not
operate normally.
All stop
Inverter current detection circuit
detected over-current and
stopped.
All stop
Over-current was detected
several seconds after header
compressor had started.
Check item (position)
• IGBT built-in temp sensor error
→ Exchange IPDU P .C. board.
• Check installation of TE1 sensor and TL sensor.
• Check characteristics of TE1 and TL sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of high-pressure Pd sensor connector.
• Check connection of low-pressure Ps sensor connector.
• Check pressure sensors Pd and Ps error.
• Check outdoor P .C. board (I/F) error.
• Check compression error of compressor.
• Misconnection of Ps sensor and Pd sensor connectors
• Check connection of Ps sensor connector.
• Check Ps sensor error.
• Check compression error of compressor.
• Check 4-way valve error.
• Check outdoor P .C. board (I/F) error.
• Check SV4 circuit error.
• Check connection of Pd sensor connector.
• Check Pd sensor error.
• Check outdoor P .C. board (I/F) error.
• Check indoor P .C. board error (EEPROM error).
• Check power voltage.
• Check power noise.
• Check outdoor P .C. board (I/F) error.
• Check power voltage. (AC220–240V ± 10%).
• Check compressor error.
• Check cause of abnormal overload operation.
• Check outdoor P .C. board (IPDU) error.
• Check compressor error.
• Check power voltage. (AC380–10%, 415V +10%).
• Check cable of compressor and phase-missing.
• Check connector/terminal connection on IPDU P .C. board.
• Check conduction of case heater.
(Check activation error due to liquid stagnation in compressor.)
• Check outdoor P .C. board (IPDU) error.
• Check outdoor MG-SW or OCR.
MG-SW : Magnet Switch, OCR : Over-current Relay