Applicable Controls - Toshiba MMU-AP0154SH1-E Installation Manual

Table of Contents

Advertisement

SMMS 1-Way Cassette SH Type
8

Applicable Controls

REQUIREMENT
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatic address
setup
It takes up to 10 minutes (usually about 3 minutes) for
the outdoor unit to start operating after the power has
been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default). If
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed by using only a
wireless remote controller, simple remote controller or
group control remote controller by itself so install a
wired remote controller separately as well.
31-EN
Installation Manual
 Basic procedure for changing
settings
Change the settings while the air conditioner is not
working. (Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table: Do
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
* The displays appearing during the setting process differ
from the ones for previous remote controllers (AMT21E,
AMT31E). (There are more CODE No.)
1
3
4
6
1
5
2
1
Push and hold
button and "TEMP."
button simultaneously for at least 4
seconds. After a while, the display flashes
as shown in the figure. Confirm that the
CODE No. is [01].
• If the CODE No. is not [01], push
button to
clear the display content, and repeat the
procedure from the beginning. (No operation of
the
remote controller is accepted for a while
after button is pushed.)
(While air conditioners are operated under the
group control, "ALL" is displayed first. When
is pushed, the indoor unit number
displayed following "ALL" is the header unit.)
(* Display content varies with the indoor unit
model.)
SMMS 1-Way Cassette SH Type
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the
louvers start swinging. The indoor unit for
change settings can be confirmed.
3
Specify CODE No. [
] with "TEMP."
buttons.
4
Select SET DATA [
] with "TIME"
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
2
repeat from Procedure
.
• To change other settings of the selected indoor
3
unit, repeat from Procedure
.
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
2
Procedure
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While
is flashing, no operation of the
remote controller is accepted.)
– 16 –
Installation Manual
 Installing indoor unit on high
ceiling
When the ceiling on which the indoor unit is to be
installed is higher than 2.7 meters, the air volume must
be adjusted so establish the high-ceiling setting.
• Follow to the basic operation procedure
1
2
3
4
5
6
(
)
3
• For the CODE No. in Procedure
, specify [5d].
4
• Select the SET DATA for Procedure
from the "List
of installable ceiling height" table in this manual.
/
▼ With a remote controller-less system (group
control)
/
Besides the switching method using the wired remote
controller as a way to establish the high ceiling setting,
switching is also possible by changing over the jumper
block settings on the indoor P.C. board as shown in the
following table.
* However, once the settings are changed, it is
necessary to reset the SET DATA to 0000 that
placing the jumper block back to the factory default
position and rewriting the SET DATA back to 0000
with wired remote controller (sold separately).
• Change over the jumper blocks on the indoor P.C.
board, and select the desired setting.
Jumper block positions (CN112, CN111 and CN110
from the left)
Jumper block position
High ceiling
MMU-
SET DATA
AP015
Short
Open
AP018
CN112 CN111 CN110
0000
3.5 m
CN112 CN111 CN110
0001
4.0 m
CN112 CN111 CN110
0003
4.2 m
AP024
3.8 m
EN