Applicable Controls - Toshiba RAV-HM301SDTY-E Installation Manual

Hide thumbs Also See for RAV-HM301SDTY-E:
Table of Contents

Advertisement

Available languages

Available languages

IM_D0X7205001-01_EN.book Page 135 Friday, May 19, 2023 9:06 PM
 Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the indoor unit.
• Keep a margin (Approx. 100 mm) on a wire to hang down the electrical control box at servicing or other purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
1. Before performing wiring work in the electrical control box, remove the cover of the box (fixed with 1 screw).
2. Tighten the screws of the terminal block firmly, and fix the wires with the cord clamp attached to the electrical
control box. (Do not apply tension to the connecting section of the terminal block.)
Mount the cover of the electrical control box without pinching wires.
Earth screw
Control wire between
indoor and outdoor units
Power supply wire
Remote controller wire
10
1
2
3
10
50
30
Earth wire
Power supply wires
(control wiring)
 Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Remote controller wire
(Locally procured)
Terminal block for remote
A
B
controller wiring of indoor unit
53-EN
– 135 –
Side C (Space: 4 mm)
Side D (Space: 8.5 mm)
Select side C or D for the power supply wire clamping
position, refer to the following table according to the cord
type and diameter.
* The cord clamp can be attached on either right or left side.
Clamp two cords side-by-side for twin connection.
Cord clamping
Wire type
Specification
position
3-core stranded wire 2.5 mm²
Side D
Cabtyre
cord
4-core stranded wire 1.5 mm²
Side C
See the figure on
the left for system
interconnection
wires to the
terminal block.
Power supply wires
Terminal block
A
Remote controller unit
B
9

Applicable controls

REQUIREMENT
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of
trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatically
address setup, it takes up to 10 minutes (usually
about 3 minute) for the outdoor unit to start operating
after the power has been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default). If
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a wireless
remote controller and simple remote controller by itself
so install a wired remote controller separately as well.
 Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU11*
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
CAUTION
Set only the Code No. shown in the following table: Do
NOT set any other Code No.
If a Code No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
3,6
2,4,5
4,5
1
7
1
Push and hold menu button and [
] setting
button simultaneously for 10 seconds or more.
• After a while, the display flashes as shown in the
figure. "ALL" is displayed as indoor unit numbers
during initial communication immediately after the
power has been turned on.
Indoor unit No.
2
Each time [
] [
] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs. The
indoor unit can be confirmed for which to change
settings.
3
Push OFF timer button to confirm the
selected indoor unit.
Code No.
Set data
54-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-hm401sdty-eRav-hm561sdty-eRav-hm801sdty-e

Table of Contents