Configuring Inputs Di1 And Di2 - Johnson Controls T600HPN-4 Installation Instructions Manual

T600hpx-4 and t600hpx-4+pir series heat pump thermostat controllers
Table of Contents

Advertisement

Configuring the T600HPx-4 or T600HPx-4+PIR
Series Thermostat Controller
The T600HPx-4 and T600HPx-4+PIR Series
Thermostat Controllers come from the factory with
default settings for all configurable parameters. The
default settings are shown in Table 2. To reconfigure
the parameters via the thermostat controller, follow the
steps in this section.
1. To access the Installer Configuration Menu,
press and hold the MENU key for approximately
8 seconds.
Note: If the Password parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed. Use the UP/DOWN arrow keys to
indicate the configured password, then press the
YES key to proceed through the Installer Configuration
Menu parameters.
2. Once the Installer Configuration Menu begins,
press the NO key to scroll through the parameters
listed in Table 2.
Table 2: Installer Configuration Menu (Part 1 of 7)
Parameter
Description and Default
Appearing
on Display
Pswrd
Sets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu.
Configuration of Digital Input 1.
1
DI1
Default: None
T600HPx-4 and T600HPx-4+PIR Series Heat Pump Thermostat Controllers Installation Instructions
3. When the desired parameter is displayed, use the
YES key to choose the desired selection option.
4. Press the YES key and then the NO key to
continue scrolling through the parameters.
To exit the Installer Configuration Menu at any time,
press the MENU key, then at the exit prompt, press the
YES key. To pass over a parameter without changing it,
press the NO key.
When the thermostat controller is in the Installer
Configuration Menu and left unattended for
approximately 8 seconds, the thermostat controller
reverts to the Status Display Menu.

Configuring Inputs DI1 and DI2

When DI1 and DI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
Each input can be configured to the Selection Options
included in Table 2.
Selection Options
Range: 0 to 1,000
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the thermostat controller
when the input is energized. Tie this input into the air conditioning
unit control card, which provides an alarm if a malfunction occurs.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat controller.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(Fan lock): A backlit flashing Fan lock alarm is displayed on the
thermostat controller when the input is not energized. This alarm is
used in conjunction with a local airflow sensor connected to the
input. The thermostat controller heating or cooling action is locked
out if no airflow is detected 10 seconds after the fan (Terminal G) is
energized. Contact open = no airflow; contact closed = airflow
present.
7