Selecting The System Mode; Selecting The Fan Mode - Johnson Controls T600HPN-4 Installation Instructions Manual

T600hpx-4 and t600hpx-4+pir series heat pump thermostat controllers
Table of Contents

Advertisement

Selecting the System Mode

The thermostat controller has four system modes:
Automatic Mode (auto): Automatic changeover
between heating and cooling. This is the default
setting.
Cooling Mode (cool): Cooling operation only.
Heating Mode (heat): Heating operation only.
Off Mode (off): The thermostat controller is off;
however, when the frost protection
(Frost pr parameter) is enabled, the thermostat
controller still calls for heat if the temperature falls
below 42°F/5.5°C.
To set the system mode while in the Main User Menu:
1. Press the NO key for all prompts until the system
mode prompt appears on the display. Press the
YES key to select the desired system mode.
2. Press the UP/DOWN arrow keys to locate the
desired system mode. Press the YES key to select
the desired system mode.
3. Press the YES key to return to the Status Display
Menu or press the NO key to return to the system
mode selection menu.

Selecting the Fan Mode

The thermostat controller has three fan mode settings:
On Fan Mode (on): Energizes the fan all the time
for both Occupied and Unoccupied states, even if
the system mode is set to off.
Automatic Fan Mode (auto): Energizes the fan
only on a call for heating or cooling, for both
Occupied and Unoccupied states. This is the
default setting for the T600HPN-4 and
T600HPN-4+PIR models.
Note: The setting for the Fan cont parameter may
affect the fan operation on a call for heating.
Smart Fan Mode (smart): Energizes the fan all
the time for Occupied states, and only on a call for
heating or cooling in Unoccupied states. This is the
default setting for the T600HPP-4 and
T600HPP-4+PIR models.
To select the fan mode while in the Main User Menu:
1. Press the NO key for all prompts until the fan mode
prompt appears on the display. Press the YES key
to set the fan mode.
2. Press the UP/DOWN arrow keys to locate the
desired fan mode. Press the YES key to select the
desired fan mode.
16
T600HPx-4 and T600HPx-4+PIR Series Heat Pump Thermostat Controllers Installation Instructions
3. Press the YES key to return to the Status Display
Menu or press the NO key to return to the fan
mode selection menu.
Programming the Daily Schedule – Two-Event
(T600HPP-4 and T600HPP-4+PIR Models)
The schedule-setting menu is used to enter the
Occupied or Unoccupied states for each day of the
week. The schedule-setting menu reflects either a
two- or a four-event schedule per day, based on what
was selected in the 2/4event parameter during the
configuration process. If the schedule-setting menu
does not reflect a two-event schedule, select two
events in the 2/4event parameter of the Installer
Configuration Menu.
When changing the time, press and release the
UP/DOWN arrow keys to change the time in 1-minute
increments; press and hold down the keys to change
the time in 30-minute increments.
Note: Programming one of the digital inputs to remote
NSB disables the menu.
To set the time schedule for a two-event schedule,
follow the steps in Table 5. See Table 7, Events 1
and 2, for an example of a two-event office schedule.
Table 5: Programming the Daily Schedule –
Two-Event (Part 1 of 2)
Thermostat
Description
Controller
Display
Press the MENU key while in the
Status Display Menu to enter the
RoomTemp
Main User Menu.
75.0°F
Press the NO key for all prompts until
the schedule set prompt appears on
Schedule
the display. Press the YES key to
set? Y/N
enter the scheduling menu.
Press the YES key to set the
schedule for Monday or press the
Monday
NO key to advance to Tuesday.
set? Y/N
Press the YES key to set the
Occupied start time for Monday or
Occupied
press the NO key to advance to
day? Y/N
Tuesday. Selecting NO leaves the
thermostat controller in the
Unoccupied state for the entire day.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T600hpn-4+pirT600hpp-4T600hpp-4+pir

Table of Contents