Table 2: Installer Configuration Menu (Part 4 of 7)
Parameter
Description and Default
Appearing
on Display
Fan cont
Determines how the fan is activated
in response to a call for heating.
Default: on
Note: The Fan cont parameter
applies to W1 when the fan is in the
Auto mode only. The Fan cont
parameter does not affect fan
operation on a call for cooling (Y1).
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
Note: The fan delay is only active
when the fan is in the Auto mode.
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
thermostat controller is in the
Unoccupied mode) when a
Schedule Override Function is
enabled using either the Main User
Menu or DI1 or DI2 configured as a
temporary override remote contact
(RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the
UP/DOWN arrow keys.
Default: 3.0 hrs
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Cal OS
Sets the desired outside air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
HP stage
Sets the number of heat pump
compressor stages.
Default: 2.0
Note: Reverts the operation of a
two-stage thermostat controller to a
one-stage thermostat controller
when the second cooling stage is
not needed.
10
T600HPx-4 and T600HPx-4+PIR Series Heat Pump Thermostat Controllers Installation Instructions
Selection Options
(off): The thermostat controller does not activate the fan in
response to a call for heating. The fan is activated by the equipment
fan and limit control.
(on): Enables the thermostat controller to activate the fan in
response to a call for heating.
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
increments
(1.0): One Stage
(2.0): Two Stages