Programming Overview

Three menus are used to view, program, and configure
the T600HPx-4 and T600HPx-4+PIR Series
Thermostat Controllers: the Status Display Menu, the
Main User Menu, and the Installer Configuration Menu.
Status Display Menu
The Status Display Menu is displayed during normal
thermostat controller operation, and continuously
scrolls through the following parameters:
Room Temperature
Day and Time (T600HPP-4 and T600HPP-4+PIR
Models)
System Mode
Schedule Status
(Occupied/Unoccupied/Override [PIR Models])
Outside Temperature – An outside air temperature
sensor must be installed and connected.
Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note: Press the YES key to temporarily stop this
menu from scrolling.
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature parameter.
Main User Menu
Use the Main User Menu to access and change the
basic operating parameters of the thermostat controller.
Access the menu by pressing the MENU key during
normal thermostat controller operation.
Installer Configuration Menu
Use the Installer Configuration Menu to set up the
thermostat controller for application-specific operation.
To access the menu, press and hold the MENU key for
approximately 8 seconds.
Unocc Heat
= 65°F
6
T600HPx-4 and T600HPx-4+PIR Series Heat Pump Thermostat Controllers Installation Instructions
Occ Heat
= 72°F
Room Temperature
Figure 9: Increasing Room Temperature Setpoints
Occupancy Sensor Operation –
T600HPx-4+PIR Series Thermostat Controllers
A T600HPx-4+PIR Series Thermostat Controller (or a
T600HPx-4 Series Thermostat Controller equipped
with a PIR accessory cover) provides advanced
occupancy logic.
Note: The PIR strategy is an occupied strategy. If the
thermostat controller is programmed to be Unoccupied,
the PIR function does not have an affect on the
occupancy strategy.
The thermostat controller automatically switches the
occupancy level between Occupied and Unoccupied as
required, when local movement is sensed. In the
Occupied mode, if no movement is detected beyond
the Unocc TM parameter setting, the mode changes to
Unoccupied. Once movement is detected, the mode
changes back to Occupied.
Occupancy sensing is enabled only if a PIR cover is
installed. The PIR cover, when installed, is auto
detected.
PIR Diagnostic LEDs
The diagnostic LEDs inside the PIR lens brighten when
movement is detected within the first 30 minutes after
powerup. The LEDs do not light up or brighten after the
initial 30-minute period.
Setpoints
The installer must be certain that the difference
between the Occupied and Unoccupied setpoints can
be recovered within a timely fashion to ensure
occupancy comfort. In addition, the difference between
the two setpoints must be large enough to warrant
maximum energy savings.
These setpoints and Unoccupied timers are adjustable
to allow for customization, as dictated by the individual
space requirements. See Figure 9 for an example of
increasing room temperature setpoints.
Occ Cool
= 75°F